Skip to main content
Schneider Electric A9N2P25CIN — 2-Pole MCB (DIN Rail)

Schneider Electric A9N2P25CIN Acti9 xC60 MCB, 25 A, C-Curve,

MPNA9N2P25CIN
Active

Schneider Electric Acti9 xC60 miniature circuit breaker, A9N2P25CIN, 2-pole, 25 A, C-curve, 10 kA breaking capacity at 415 V AC, 35 mm DIN rail clip-on.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9N2P25CIN — Identification
ParameterValue
Product nameXC60
Product rangeActi9
Series / familyActi9
Device short namexC60
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9N2P25CIN — Electrical
ParameterValue
Rated current [In]25 A
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 100...125 V DC
Network type (AC/DC)DC AC
Network frequency50/60 Hz
A9N2P25CIN — Protection
ParameterValue
Tripping curve codeC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity (Icu)10 kA Inc at 380...415 V AC 50/60 Hz conforming to IS/IEC 60947-2 6 kA Icu at 100...125 V DC conforming to IS/IEC 60947-2
Rated service breaking capacity [Ics]6 kA conforming to IS/IEC 60947-2 - 100...125 V DC 7.5 kA conforming to IS/IEC 60947-2 - 380...415 V AC 50/60 Hz
Energy limitation class3 conforming to IS/IEC 60947-2
Suitable for isolationYes conforming to IS/IEC 60947-2
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
A9N2P25CIN — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height85 mm
Depth77.5 mm
Mounting support35 mm DIN rail
Mounting modeClip-on
Terminal connectionsTunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)
Terminal tightening torque2 N.m
Comb busbar / distribution block compatibilityTop: YES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
A9N2P25CIN — Environmental
ParameterValue
Operating temperature range-30...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
A9N2P25CIN — Approvals
ParameterValue
Standards / complianceIS/IEC 60947-2

Product details

The Schneider Electric A9N2P25CIN is a 2-pole miniature circuit breaker from the Acti9 xC60 range, rated 25 A with a C-curve trip characteristic. The C-curve means magnetic tripping occurs at 8 x In (200 A) ±20% — designed for inductive loads like motor starters and small transformers where inrush current exceeds resistive load levels. The 10 kA breaking capacity at 380…415 V AC (IS/IEC 60947-2) tells you this MCB can safely interrupt a fault current up to 10,000 A without welding its contacts or cascading failure upstream. For DC circuits, the rated breaking capacity is 6 kA at 100…125 V DC, so it handles moderate DC faults but not high-voltage DC bus work.

Width is 36 mm — 4 x 9 mm pitches — so it occupies two standard modular positions on the rail. Depth of 77.5 mm and height of 85 mm mean it fits most distribution boards without crowding the gland plate. Wire stripping length is 13 mm for top or bottom connection. IP20 finger-safe protection is fine for enclosed panels; not rated for washdown environments.

Limitation class 3 per that standard means it limits let-through energy well — useful for downstream component protection.

Frequently asked questions

How do I get current pricing and availability for A9N2P25CIN?

The A9N2P25CIN is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of A9N2P25CIN?

The breaking capacity is 10 kA at 380…415 V AC (Icn per IS/IEC 60947-2) and 6 kA at 100…125 V DC (Icu per the same standard).

What does the C-curve mean on this MCB?

The C-curve means magnetic tripping occurs at 8 x In (200 A) ±20%, making it suitable for inductive loads like motor starters and small transformers that draw moderate inrush current.

What compliance documentation does this brand provide for A9N2P25CIN?

The MCB is certified to IS/IEC 60947-2, carries tropicalisation class 2 per IEC 60068-1, and is rated pollution degree 3. Specific RoHS/REACH/UL documentation would be provided by the supplier at time of order.

MPN
A9N2P25CIN