Skip to main content
Schneider Electric A9N60708 — 1-Pole MCB (DIN Rail)

Schneider Electric A9N60708 Acti9 C120 MCB, 80 A, 1P, C-Curv

MPNA9N60708
Active

Schneider Electric Acti9 C120, miniature circuit breaker, 1P, 80 A, C-curve, 5 kA Icu at 230...400 V AC, thermal-magnetic, clip-on DIN rail.

$23.09Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9N60708 — Identification
ParameterValue
Product nameActi9 C120
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameC120a
Poles description1P
Number of protected poles1
Device applicationDistribution
A9N60708 — Electrical & Protection
ParameterValue
Rated current (In)80 A at 40 °C
Rated operational voltage (Ue)230...400 V AC 50/60 Hz
Tripping curve codeC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity (Icu / AIR)5 kA Icu at 230...400 V AC 50/60 Hz conforming to EN/IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Overvoltage categoryIII
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9N60708 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals1 cable(s) 1...50 mm² rigid Tunnel type terminals1 cable(s) 1.5...35 mm² flexible
Mounting support35 mm symmetrical DIN rail
Mounting modeClip-on
Width27 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)Power circuit: 3.5 N.m top or bottom
A9N60708 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to IEC 60529
A9N60708 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2
A9N60708 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

The Schneider Electric A9N60708 is a 1-pole miniature circuit breaker from the Acti9 C120 range, rated 80 A at 40 °C with a C-curve trip characteristic. It clips onto a 35 mm symmetrical DIN rail — standard for panel and enclosure builds — and occupies 3 x 9 mm pitches (27 mm wide). The thermal-magnetic trip unit handles distribution-level overcurrent and short-circuit protection, with a magnetic tripping limit of 8 x In ±20 %.

Rated 5 kA Icu at 230...400 V AC 50/60 Hz per EN/IEC 60947-2. The limitation class is 3 per the same standard, meaning it lets through less energy during a fault, which helps with downstream coordination.

Installation and wiring constraints

Tunnel-type terminals accept 1...50 mm² rigid or 1.5...35 mm² flexible cable. Wire stripping length is 15 mm for both top and bottom connections. Tightening torque: 3.5 N·m. The toggle gives local ON/OFF indication, and the contact position indicator confirms the state visually. Padlock provision is included for lockout/tagout procedures.

Frequently asked questions

What is the breaking capacity of A9N60708?

5 kA Icu at 230...400 V AC 50/60 Hz, conforming to EN/IEC 60947-2. That is the maximum fault current it can safely interrupt.

Where can I buy A9N60708?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the width of A9N60708 on a DIN rail?

27 mm, which corresponds to 3 x 9 mm pitches on a 35 mm symmetrical DIN rail.

MPN
A9N60708