Skip to main content
Schneider Electric A9P54306 — Miniature Circuit Breakers (MCB)

Schneider Electric A9P54306 Acti9 iC40 MCB, 6 A, C-Curve, 3P

MPNA9P54306
Active

Schneider Electric Acti9 iC40N miniature circuit breaker, A9P54306, 6 A rated current, C-curve, 3-pole, 10 kA breaking capacity at 400 V AC per IEC 60947-2, thermal-magnetic trip, clip-on DIN rail mount.

$116.42Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9P54306 — Identification
ParameterValue
Product nameActi9 iC40
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9P54306 — Ratings
ParameterValue
Rated current (In)6 A
Poles configuration3P
Number of protected poles3
Breaking capacity10 kA Icu at 400 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)6000 A 100 % x Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 7.5 kA 75 % x Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated operational voltage (Ue)400 V AC 50/60 Hz
Rated insulation voltage (Ui)440 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)4 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
A9P54306 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit5...10 x In conforming to EN/IEC 60898-1 8 x In +/- 20 % conforming to EN/IEC 60947-2
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)20000 cycles
Mechanical durability (cycles)20000 cycles
A9P54306 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Terminal connection typeTunnel type terminals top or bottom 1...10 mm² flexible Tunnel type terminals top or bottom 1...16 mm² rigid
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationON/OFF indication Trip indicator
Width54 mm
Height85 mm
Depth74 mm
Number of 9 mm pitches6
A9P54306 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
A9P54306 — Approvals
ParameterValue
StandardsEN/IEC 60898-1 EN/IEC 60947-2

Product details

Acti9 iC40N — 6 A, C-curve, 3-pole miniature circuit breaker

It's a 3-pole unit rated at 6 A with a C-curve trip characteristic, meaning magnetic tripping occurs between 5 and 10 times the rated current per EN/IEC 60898-1, and at 8 x In ±20% per EN/IEC 60947-2. Breaking capacity is 10 kA Icu at 400 V AC per IEC 60947-2, with an Icn of 6000 A at 400 V per IEC 60898-1. That dual rating gives you selectivity headroom in a typical distribution board — the 10 kA ultimate rating governs fault clearing upstream; the 6 kA service rating covers the downstream branch. The thermal-magnetic trip unit covers sustained overloads and short circuits.

Width is 54 mm (6 x 9 mm pitches), height 85 mm, depth 74 mm. That footprint is common across the Acti9 range — if you're swapping an existing iC40 or iC60 unit, the busbar alignment and enclosure cutout should match. The IP20 terminal protection (IP40 on the modular enclosure per IEC 60529) meets typical panel requirements — not rated for washdown, but fine inside a closed cabinet. Operating altitude is rated to 2000 m without derating.

The breaker carries quality labels from OVE and AENOR, and is certified to the harmonized standards EN/IEC 60898-1 and EN/IEC 60947-2. Compliance documentation (declaration of conformity) is available from the manufacturer for your QA file. This is a standard distribution product — not a safety-rated device with a TÜV SIL certificate, but the isolation suitability and dual-standard breaking capacity give you the typical documentation for an IEC panel.

Frequently asked questions

What is A9P54306's breaking capacity?

10 kA Icu at 400 V AC per IEC 60947-2, and 6000 A Icn at 400 V AC per IEC 60898-1. The dual rating covers both ultimate fault clearing and service-level short-circuit performance.

MPN
A9P54306