Skip to main content
Schneider Electric A9TDF3610 — Residual Current Breakers (RCCB/RCBO)

A9TDF3610 Acti9 iCV40N ARC 10A C-Curve AFDD+MCB, 6kA

MPNA9TDF3610
Active

Schneider Electric Acti9 iCV40N ARC, 1P+N, 10 A, C-curve, 6 kA Icn / 10 kA Icu, arc fault detection device (AFDD) + MCB combination, DIN-rail mount.

$323.68Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9TDF3610 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A-SI (Super Immunised)
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip LED arc fault diagnostic
A9TDF3610 — Electrical Ratings
ParameterValue
Rated current (In)10 A
Rated operational voltage (Ue)230 V AC 50 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)250 V AC 50 Hz between phase and neutral
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII
Device location in systemOutgoer
Electrical durability20000 cycles 230 V AC 50 Hz
Mechanical durability (operating cycles)20000 cycles
A9TDF3610 — Identification
ParameterValue
Product nameActi9 iCV40 ARC
Product / component typeArc fault detection RCBO
Product range / familyActi9
Device short nameiCV40N ARC
A9TDF3610 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminal 1...16 mm² rigid Tunnel type terminal 1...10 mm² flexible
Wire stripping length14 mm
Terminal tightening torque2 N.m
Width36 mm
Height91 mm
Depth73 mm
A9TDF3610 — Environmental
ParameterValue
Operating ambient temperature-25...50 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree2 conforming to EN/IEC 62606
Relative humidity95 % at 55 °C
Operating altitude2000 m
TropicalisationSeverity B conforming to IEC 60068-2-30 for 28 d
A9TDF3610 — Approvals
ParameterValue
StandardsEN/IEC 62606 EN/IEC 61009-1 EN/IEC 60947-2 EN/IEC 61009-2-1

Product details

Arc-fault + overcurrent in one 36 mm module

The A9TDF3610 is a Schneider Electric Acti9 iCV40N ARC — a combined arc-fault detection device (AFDD) and miniature circuit breaker in a single 1P+N, 36 mm wide DIN-rail module. It carries a 10 A rated current with a C-curve magnetic trip (5–10 x In) and a 6 kA Icn / 10 kA Icu breaking capacity at 230 V AC, 50 Hz, per EN/IEC 61009-2-1 and EN/IEC 60947-2. The arc-fault detection is the primary differentiator here: it monitors for the high-frequency signature of a series or parallel arc (e.g., a loose terminal, a crushed cable) and trips before the arc has time to propagate into a panel fire. The diagnostic LED on the toggle gives a local indication of an arc-fault trip versus an overload or short — saves the commissioning engineer a clamp-meter hunt on a nuisance-trip callout.

What the 6 kA Icn / 10 kA Icu means for your panel

The 6 kA Icn (rated short-circuit capacity per EN/IEC 61009-2-1) is the breaker's tested interrupting rating under the MCB standard — it clears a 6 kA fault at 230 V and remains serviceable afterward. The 10 kA Icu (ultimate breaking capacity per EN/IEC 60947-2) is the higher one-shot rating under the industrial standard; the breaker will interrupt a 10 kA fault but may need replacement afterward. For most commercial and light-industrial distribution boards with a prospective fault current under 6 kA, the Icn figure governs the daily duty. The 10 kA Icu gives headroom for a stronger upstream transformer or a closer fault location without cascading. The C-curve (5–10 x In) means the magnetic trip fires between 50 A and 100 A — suitable for general-purpose loads with moderate inrush, like lighting banks, small motor circuits, or socket outlets. The thermal-magnetic trip mechanism is a traditional bimetal + solenoid, field-reliable and predictable.

Cable entry from top or bottom — no forced feed direction, which helps with busbar or loop-through wiring in a crowded enclosure. Pollution degree 2 (non-conductive dust, occasional condensation) per EN/IEC 62606.

Frequently asked questions

Who supplies A9TDF3610 and how is it quoted for volume purchases?

The A9TDF3610 is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What is A9TDF3610's listed depth (73 mm) on this component line?

The A9TDF3610 has a depth of 73 mm, a width of 36 mm (4 x 9 mm pitches), and a height of 91 mm — standard modular dimensions for a 1P+N DIN-rail device.

What compliance documentation does this brand provide for A9TDF3610 (RoHS, REACH, UL, IEC)?

The A9TDF3610 is certified to EN/IEC 62606 (arc-fault detection), EN/IEC 61009-1, EN/IEC 60947-2, and EN/IEC 61009-2-1. It carries IMQ, AENOR, and OVE quality labels. RoHS/REACH declarations are standard for the Acti9 range and available on request.

What is A9TDF3610's listed range (Acti9) on this component line?

The A9TDF3610 belongs to the Schneider Electric Acti9 range, specifically the iCV40N ARC series — a combined AFDD + MCB in a 1P+N form factor.

MPN