Schneider Electric A9TDF3616 — Residual Current Breakers (RCCB/RCBO)

A9TDF3616 Acti9 iCV40 ARC 1P+N 16A C-curve RCBO, 6kA/10kA

MPNA9TDF3616
Active

Schneider Electric Acti9 iCV40 ARC RCBO, 1P+N, 16 A, C-curve, 6 kA Icn / 10 kA Icu at 230 V AC, DIN-rail clip-on, white (RAL 9003).

$323.68Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9TDF3616 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A-SI (Super Immunised)
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip LED arc fault diagnostic
A9TDF3616 — Electrical Ratings
ParameterValue
Rated current (In)16 A
Rated operational voltage (Ue)230 V AC 50 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)250 V AC 50 Hz between phase and neutral
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII
Device location in systemOutgoer
Electrical durability20000 cycles 230 V AC 50 Hz
Mechanical durability (operating cycles)20000 cycles
A9TDF3616 — Identification
ParameterValue
Product nameActi9 iCV40 ARC
Product / component typeArc fault detection RCBO
Product range / familyActi9
Device short nameiCV40N ARC
A9TDF3616 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminal 1...16 mm² rigid Tunnel type terminal 1...10 mm² flexible
Wire stripping length14 mm
Terminal tightening torque2 N.m
Width36 mm
Height91 mm
Depth73 mm
A9TDF3616 — Environmental
ParameterValue
Operating ambient temperature-25...50 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree2 conforming to EN/IEC 62606
Relative humidity95 % at 55 °C
Operating altitude2000 m
TropicalisationSeverity B conforming to IEC 60068-2-30 for 28 d
A9TDF3616 — Approvals
ParameterValue
StandardsEN/IEC 62606 EN/IEC 61009-1 EN/IEC 60947-2 EN/IEC 61009-2-1

Product details

The Schneider Electric A9TDF3616 is an Acti9 iCV40 ARC residual current circuit breaker with overcurrent protection (RCBO), 1P+N, rated 16 A with a C-curve magnetic trip characteristic (5...10 x In). It breaks 6 kA Icn per EN/IEC 61009-2-1 and 10 kA Icu per EN/IEC 60947-2 at 230 V AC, 50 Hz — enough for most residential and light commercial final circuits where fault levels stay under 10 kA. The thermal-magnetic trip unit handles overload and short-circuit; the integrated residual current element adds earth-leakage protection in one 36 mm wide DIN-rail module.

The 16 A rated current and C-curve (5–10 x In magnetic trip) suit general-purpose socket circuits, lighting, and small appliance loads where inrush is moderate — think office power outlets or domestic ring mains. The 6 kA Icn is the service breaking capacity for routine faults; the 10 kA Icu is the ultimate breaking capacity for rare high-fault events, giving the installer headroom in selectivity coordination with an upstream 10 kA-rated MCB or fuse. IP20 rated — suitable for enclosed distribution boards only. The toggle control with ON/OFF/fault-trip LED and arc-fault diagnostic signalling gives a quick visual on the circuit state.

Frequently asked questions

What is A9TDF3616's listed range (Acti9) on this component line?

It belongs to the Acti9 range, Schneider Electric's modular DIN-rail protection and control family for final distribution.

MPN
A9TDF3616