Skip to main content
Schneider Electric A9TPDD610 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9TPDD610 Acti9 iC40N ARC, 10 A, 1P+N, B-

MPNA9TPDD610
Active

Schneider Electric Acti9 Active ARC iC40N, A9TPDD610, 10 A rated, 1P+N, B-curve, 6 kA Icn at 230 V AC, clip-on DIN-rail mount, IP20.

$353.05Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9TPDD610 — Residual Current Protection
ParameterValue
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip LED arc fault diagnostic
A9TPDD610 — Electrical Ratings
ParameterValue
Rated current (In)10 A
Rated operational voltage (Ue)230 V AC 50 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)250 V AC
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durability10000 cycles
Mechanical durability (operating cycles)20000 cycles
A9TPDD610 — Identification
ParameterValue
Product nameActi9 Active ARC iC40
Product / component typeActive arc fault detection circuit breaker
Product range / familyActi9
Device short nameiC40N ARC
A9TPDD610 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminal 1...10 mm² flexible Tunnel type terminal 1...16 mm² rigid
Wire stripping length14 mm
Terminal tightening torque2 N.m
Width36 mm
Height91 mm
Depth73 mm
A9TPDD610 — Environmental
ParameterValue
Operating ambient temperature-25...40 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree2
Operating altitude2000 m
TropicalisationSeverity B conforming to IEC 60068-2-30 for 28 d
A9TPDD610 — Approvals
ParameterValue
StandardsEN/IEC 60898-1 EN/IEC 60947-2 EN/IEC 62606

Product details

It complies with EN/IEC 60898-1 (MCB standard), EN/IEC 60947-2 (low-voltage switchgear), and EN/IEC 62606 (arc-fault detection), so it meets the requirements for arc-fault protection in many national wiring regulations.

The breaking capacity is 6000 A Icn per EN/IEC 60898-1 at 230 V AC, and 10 kA Icu per EN/IEC 60947-2 — enough for most residential and light-commercial service-entrance fault levels. The 3000 A Icn1 rating (60898-1) covers the lower end of the standard's test sequence. Clip-on mounting to a 35 mm DIN rail (EN 60715) and a width of 36 mm (4 x 9 mm pitches) mean it occupies a single module space in a consumer unit or distribution board. The IP20 finger-safe terminals are standard for enclosed panels. Local signalling includes ON/OFF position and a fault-trip LED with arc-fault diagnostics.

Installation notes

Tunnel-type terminals accept 1–10 mm² flexible or 1–16 mm² rigid copper. Cable entry from top or bottom, neutral on the left. Rated for 2000 m operating altitude, pollution degree 2, and tropicalisation severity B (28-day damp-heat cycle per IEC 60068-2-30). Electrical durability is 10 000 cycles, mechanical durability 20 000 cycles.

Frequently asked questions

What is the breaking capacity of the A9TPDD610?

The breaking capacity is 6000 A Icn per EN/IEC 60898-1 at 230 V AC, and 10 kA Icu per EN/IEC 60947-2.

What standards does the A9TPDD610 comply with?

It complies with EN/IEC 60898-1, EN/IEC 60947-2, and EN/IEC 62606 (arc-fault detection).

MPN