Skip to main content
Schneider Electric A9TPED640 — Residual Current Breakers (RCCB/RCBO)

Schneider A9TPED640 Acti9 iC40N ARC MCB, 40 A, 1P+N, C-curve

MPNA9TPED640
Active

Schneider Electric Acti9 Active ARC iC40N, A9TPED640, 1P+N miniature circuit breaker, 40 A rated, C-curve, 10 kA Icu at 230 V AC, DIN-rail mount, IP20.

$353.05Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9TPED640 — Residual Current Protection
ParameterValue
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip LED arc fault diagnostic
A9TPED640 — Electrical Ratings
ParameterValue
Rated current (In)40 A
Rated operational voltage (Ue)230 V AC 50 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)250 V AC
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durability10000 cycles
Mechanical durability (operating cycles)20000 cycles
A9TPED640 — Identification
ParameterValue
Product nameActi9 Active ARC iC40
Product / component typeActive arc fault detection circuit breaker
Product range / familyActi9
Device short nameiC40N ARC
A9TPED640 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminal 1...10 mm² flexible Tunnel type terminal 1...16 mm² rigid
Wire stripping length14 mm
Terminal tightening torque2 N.m
Width36 mm
Height91 mm
Depth73 mm
A9TPED640 — Environmental
ParameterValue
Operating ambient temperature-25...40 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree2
Operating altitude2000 m
TropicalisationSeverity B conforming to IEC 60068-2-30 for 28 d
A9TPED640 — Approvals
ParameterValue
StandardsEN/IEC 60898-1 EN/IEC 60947-2 EN/IEC 62606

Product details

The Schneider Electric A9TPED640 is an Acti9 Active ARC iC40N miniature circuit breaker (MCB) — a single-pole-plus-neutral device rated 40 A with a C-curve trip characteristic, built for AC networks at 50 Hz. It sits on a DIN rail in the outgoing feeder position of a distribution board, protecting branch circuits against overload and short-circuit faults.

Breaking capacity — what the three numbers mean

This breaker carries three breaking-capacity ratings, each tied to a different standard. At 230 V AC, 50 Hz: 3000 A Icn per EN/IEC 60898-1 (the domestic/commercial MCB standard), 6000 A Icn per the same standard, and 10 kA Icu per EN/IEC 60947-2 (the industrial standard for switchgear). The lower Icn values reflect the less demanding test sequence of the MCB standard. For a cement plant or similar dusty environment, the 10 kA SCCR headroom means this part coordinates cleanly with a downstream 40 A load and an upstream feeder breaker sized for the panel's available fault current.

Width is 36 mm, height 91 mm, depth 73 mm. Clips onto a DIN rail. Neutral on the left, supply cable entry at top or bottom.

Measurement and diagnostics — what the accuracy tells you

The iC40N ARC variant includes embedded measurement of voltage, current, active power, and power factor, with stated accuracy: ±2 % for voltage and current, ±5 % for power.

Frequently asked questions

What is the breaking capacity of A9TPED640?

At 230 V AC, 50 Hz: 3000 A Icn and 6000 A Icn per EN/IEC 60898-1, and 10 kA Icu per EN/IEC 60947-2. The 10 kA Icu is the industrial rating that governs fault interruption in a panel.

What is the closest alternative to A9TPED640 in the Acti9 family?

The closest alternative is the standard iC40N (non-ARC) version, which omits the arc-fault detection and embedded measurement functions but shares the same 40 A C-curve, 1P+N, 10 kA Icu, and DIN-rail footprint. If arc-fault detection is not required, the standard iC40N is a direct fit at a lower cost. If arc-fault detection is mandatory, there is no pin-compatible substitute — the A9TPED640 is the only Acti9 ARC variant at this rating.

What compliance documentation does Schneider provide for A9TPED640?

The breaker carries AENOR quality label and conforms to EN/IEC 60898-1, EN/IEC 60947-2, and EN/IEC 62606. Tropicalisation per IEC 60068-2-30 severity B for 28 days. Pollution degree 2. Standard Schneider declarations of conformity and CE marking apply.

MPN
A9TPED640