A9TYAE225 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A-SI (Super Immunised)
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Local signalling / indicationON, OFF, fault trip LED arc fault diagnostic
A9TYAE225 — Electrical Ratings
ParameterValue
Rated current (In)25 A
Rated operational voltage (Ue)230 V AC
Poles description2P
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durability10000 cycles > 25 A 20000 cycles <= 25 A
Mechanical durability (operating cycles)20000 cycles
A9TYAE225 — Identification
ParameterValue
Product nameActi9 Active VigiARC iC60
Product / component typeActive arc fault detection with residual current protection add-on block
Device short nameVigiARC iC60
A9TYAE225 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Width in 9 mm modules2
Wire stripping length14 mm
Terminal tightening torque2 N.m
Width54 mm
Height91 mm
Depth73 mm
A9TYAE225 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree2
Operating altitude2000 m
TropicalisationSeverity B conforming to IEC 60068-2-30 for 28 d
A9TYAE225 — Approvals
ParameterValue
StandardsEN/IEC 62606 EN/IEC 61009-1 EN/IEC 61009-2-1

Product details

The Schneider Electric A9TYAE225 is an Active arc-fault detection device with residual-current protection — a combined AFDD + RCD add-on block from the Acti9 VigiARC iC60 range. Rated at 25 A continuous on a 230 V AC network (50 Hz), with an insulation voltage of 400 V AC. The trip threshold for overvoltage is 275 V ±5 V — meaning it catches sustained swells that could start a fire in loose connections or degraded insulation.

Built to EN/IEC 62606 (arc-fault detection devices), EN/IEC 61009-1 (RCBOs), and EN/IEC 61009-2-1 (functional). Earth-leakage protection is Type A-SI (Super Immunised), which means it resists nuisance tripping from high-frequency harmonics or transient surges common on inverter-fed circuits or long cable runs.

Clip-on mount on standard DIN rail (35 mm), 2-pitch wide (9 mm per pitch). Dimensions: 91 mm high, 54 mm wide, 73 mm deep. Terminals accept 0.2–2.5 mm² solid or stranded wire; strip length 14 mm, tighten to 2 N·m. Pollution degree 2 (normal, non-conductive). Ambient storage range -40 to 85 °C, tropicalised to severity B per IEC 60068-2-30 for 28 days — survives the nacelle or a humid panel room.

Signalling and diagnostics

Local signalling includes ON, OFF, fault-trip LED, and an arc-fault diagnostic indicator. Records date/time of events and maintenance indicators — compatible with EcoStruxure Panel Server (Entry, Advanced, Universal) for remote monitoring. Accuracy for voltage, current, and power is ±2 %; power factor measurement is ±5 %. Electrical durability: 20,000 cycles at ≤25 A, 10,000 cycles above. Mechanical durability: 20,000 cycles.

Frequently asked questions

Who supplies A9TYAE225 and how is it quoted for volume purchases?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

What are the key ratings on A9TYAE225?

Rated 25 A continuous, 30 mA earth-leakage sensitivity, 230 V AC operational voltage, 400 V AC insulation voltage, 50 Hz network frequency.

What standards does A9TYAE225 comply with?

Compliant with EN/IEC 62606 (arc-fault detection), EN/IEC 61009-1 (RCBOs), and EN/IEC 61009-2-1 (functional). Earth-leakage protection is Type A-SI (Super Immunised).