Specifications

A9W31363 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Local signalling / indicationTrip indicator
A9W31363 — Electrical Ratings
ParameterValue
Rated current (In)63 A
Rated operational voltage (Ue)400/415 V AC 50/60 Hz conforming to IEC 61009-1
Poles description3P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to IEC 60947-2
Device location in systemOutgoer
A9W31363 — Identification
ParameterValue
Product nameActi9 Vigi iC60
Product / component typeAdd-on residual current device
Product range / familyActi9
Device short nameVigi iC60
A9W31363 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Width in 9 mm modules7
Terminal connectionsTunnel type terminals downside 1...35 mm² rigid Tunnel type terminals downside 1...25 mm² flexible
Wire stripping length14 mm
Terminal tightening torque3.5 N.m
Width117 mm
Height91 mm
Depth74 mm
A9W31363 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-2
A9W31363 — Approvals
ParameterValue
StandardsIEC 61009-1 EN 61009-1

Product details

The Schneider Electric A9W31363 is an add-on residual current device (RCD) from the Acti9 Vigi iC60 range, designed to snap onto the side of an iC60 miniature circuit breaker (MCB) via the clip-on mounting. It provides earth-leakage protection for the downstream circuit, tripping the MCB when leakage exceeds the 30 mA threshold. The 63 A rated current matches the MCB it attaches to, so the pair handles the full load current of the circuit. The Type A-SI (Super Immunised) classification means it detects sinusoidal AC and pulsating DC residual currents, while being immune to nuisance tripping from high-frequency harmonics or transient surges — a requirement for circuits feeding electronic loads like VFDs, UPS systems, or IT equipment. The voltage-independent tripping technology ensures the RCD operates even if the line voltage is lost, which is a safety advantage over electronically dependent units.

The 117 mm width, 91 mm height, and 74 mm depth fit within the standard Acti9 modular enclosure footprint. The electrical connection to the MCB is via screws, so the assembly is mechanical and electrical — no extra wiring between the two devices. The IP20 rating (IP40 in modular enclosure) is suitable for dry indoor panel environments; pollution degree 3 per IEC 60947-2 covers the typical industrial panel atmosphere.

The device is designed and certified to IEC 61009-1 and EN 61009-1, the governing standards for residual current operated circuit breakers with integral overcurrent protection (RCBOs) — though this is an add-on RCD, not a combined unit, the standard applies to the residual current function. The 8/20 µs impulse withstand rating of 3000 A per IEC 61009-1 confirms it survives common surge events without damage. The local trip indicator provides visual confirmation of a residual current trip, aiding fault isolation.

MPN
A9W31363