A9W35363 Acti9 Vigi iC60 RCD, 3P 63A 300mA A-SI Selective

MPNA9W35363
Active

Schneider Electric Acti9 Vigi iC60 add-on residual current device, A9W35363, 3P, 63 A, 300 mA, Type A-SI selective, 400 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9W35363 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)300 mA
Earth-leakage trip time delaySelective
Residual-current tripping technologyVoltage independent
Local signalling / indicationTrip indicator
A9W35363 — Electrical Ratings
ParameterValue
Rated current (In)63 A
Rated operational voltage (Ue)400 V AC 50/60 Hz conforming to EN 61009-1 230/415 V AC 50/60 Hz conforming to IEC 61009-1
Poles description3P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to IEC 60947-2
Device location in systemOutgoer
A9W35363 — Identification
ParameterValue
Product nameActi9 Vigi iC60
Product / component typeAdd-on residual current device
Product range / familyActi9
Device short nameVigi iC60
A9W35363 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Width in 9 mm modules7
Terminal connectionsTunnel type terminals downside 1...35 mm² rigid Tunnel type terminals downside 1...25 mm² flexible
Wire stripping length14 mm
Terminal tightening torque3.5 N.m
Width117 mm
Height91 mm
Depth74 mm
A9W35363 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-2
A9W35363 — Approvals
ParameterValue
StandardsEN 61009-1 IEC 61009-1

Product details

The Schneider Electric A9W35363 is an Acti9 Vigi iC60 add-on residual current device — 3 poles, rated 63 A, with a 300 mA earth-leakage sensitivity. It clips onto the outgoing side of an iC60 MCB via the screw connection, adding RCD protection to that circuit without replacing the breaker. The Type A-SI (Super Immunised) classification means it handles pulsed DC fault currents from electronics (VSDs, UPS, LED drivers) that would desensitize a standard Type A, while the selective time delay (short intentional delay) coordinates with downstream RCDs so only the faulted subcircuit trips — critical for a distribution board feeding multiple loads where nuisance tripping on a main RCD shuts the whole panel.

63 A rated current matches the iC60 breaker it pairs with — the RCD does not increase the circuit ampacity, it just adds leakage detection. The 300 mA sensitivity is typical for main or submain protection where a 30 mA unit would nuisance-trip on normal cable leakage. Selective (S-type) delay gives about 40–150 ms inertia, letting downstream 30 mA RCDs clear first. Voltage-independent tripping means it operates even if the neutral is lost — the fault energy itself triggers the mechanism, no auxiliary supply needed. The 400 V AC rated operational voltage (per EN 61009-1) covers 3-phase 4-wire networks up to 415 V line-to-line.

Clip-on mounting to DIN rail, 7 x 9 mm pitches wide (117 mm). The tunnel-type terminals accept up to 35 mm² rigid or 25 mm² flexible cable, with a 3.5 N.m tightening torque and 14 mm strip length. The trip indicator gives local visual confirmation of a leakage trip, which speeds troubleshooting on a multi-circuit panel.

Frequently asked questions

What is A9W35363 used for?

It is an add-on residual current device (RCD) that mounts to the outgoing side of an iC60 MCB, adding earth-leakage protection at 300 mA with a selective time delay. The Type A-SI rating handles pulsed DC from modern electronics without nuisance tripping.

What is the difference between Type A-SI and standard Type A?

Type A-SI (Super Immunised) is designed to remain stable on circuits with pulsed DC fault currents from VSDs, UPS systems, or LED drivers — conditions that can cause a standard Type A RCD to trip falsely or fail to trip. It also includes the selective (S-type) delay for coordination with downstream RCDs.