Skip to main content
Schneider Electric A9XPH816 — Circuit Breaker Accessories

Schneider Electric A9XPH816 Acti9 Comb Busbar, 80 A, 288 mm,

MPNA9XPH816
Obsolete

Schneider Electric Acti9 comb busbar, bottom feed, 3L+N, 18 mm pitch, 16 modules, 80 A at 40 °C, 288 mm width, white (RAL 9003).

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9XPH816 — Identification
ParameterValue
Product / component typeComb busbar
Product rangeActi9
A9XPH816 — Electrical
ParameterValue
Rated operational voltage [Ue]230 V AC Ph/N 400 V AC Ph/Ph
Rated insulation voltage [Ui]500 V AC conforming to IEC 61439-1
Rated impulse withstand voltage [Uimp]6 kV
A9XPH816 — Mechanical
ParameterValue
Connection pitch18 mm
Mounting modeHorizontal
Usable 9 mm pitches32
Width288 mm
ColourWhite (RAL 9003)
A9XPH816 — Environmental
ParameterValue
IP degree of protectionIP20 with end-pieces and tooth covers
Pollution degree3 conforming to IEC 60947-7-1
A9XPH816 — Approvals
ParameterValue
StandardsIEC 60947-7-1 IEC 61439-1

Product details

It's rated 80 A at 40 °C, with a 500 V AC rated insulation voltage and operational voltage of 230 V AC phase-to-neutral or 400 V AC phase-to-phase. The 288 mm width spans 16 modules at an 18 mm pitch, making it a direct fit for Acti9 distribution boards where you need to distribute 3L+N from the bottom.

The busbar mounts horizontally on tunnel-type terminals at the bottom of the enclosure. It provides 1 incoming way (4-pole, N + 3L) and 6 outgoing ways (each 1P+N). The connection pitch is 18 mm, with 32 nine-millimeter pitches total. The marking is clearly printed: outgoer side reads N N L2 N L3, incomer side reads N L2 L3. IP20 protection is achieved with end-pieces and tooth covers fitted.

It meets IEC 60947-7-1 (busbar trunking) and IEC 61439-1 (low-voltage switchgear assemblies). The rated impulse withstand voltage is 6 kV, pollution degree 3 per IEC 60947-7-1, and the fire resistance is 960 °C for 30 seconds per IEC 60695-2-1. The bar is cuttable, so you can trim it to fit shorter runs in the panel.

Frequently asked questions

Where can I buy the A9XPH816?

The A9XPH816 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock or price is listed here.

What is the A9XPH816's current rating?

It is rated 80 A at 40 °C, with a rated insulation voltage of 500 V AC and operational voltage of 230 V AC phase-to-neutral or 400 V AC phase-to-phase.

What standards does the A9XPH816 comply with?

It complies with IEC 60947-7-1 (busbar trunking) and IEC 61439-1 (low-voltage switchgear assemblies).

MPN