Skip to main content
Schneider Electric A9Y76740 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9Y76740 Acti9 Vigi iCG40 RCD, 40A 300mA

MPNA9Y76740
Active

Schneider Electric Acti9 Vigi iCG40 add-on residual current device, 3P+N, 40 A rated, 300 mA sensitivity, Type A-SI super immunised, selective, voltage independent, clip-on DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9Y76740 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)300 mA
Earth-leakage protection class / typeType A-SI (Super Immunised)
Earth-leakage trip time delaySelective
Residual-current tripping technologyVoltage independent
Local signalling / indicationFault indication
A9Y76740 — Electrical Ratings
ParameterValue
Rated current (In)40 A
Rated operational voltage (Ue)400 V AC 50/60 Hz
Poles description3P + N
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)440 V AC 50/60 Hz conforming to EN/IEC 61009-2-1
Rated impulse withstand voltage (Uimp)4 kV conforming to EN/IEC 61009-2-1
Device location in systemGroup incomer
Electrical durability10000 cycles
Mechanical durability (operating cycles)20000 cycles
A9Y76740 — Identification
ParameterValue
Product nameActi9 Vigi iCG40
Product / component typeAdd-on residual current device
Product range / familyActi9
Device short nameVigi iCG40
A9Y76740 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Width in 9 mm modules6
Terminal connectionsTunnel type terminal top 1...16 mm² rigid Tunnel type terminal top 1...10 mm² flexible
Wire stripping length14 mm for top connection
Terminal tightening torque2 N.m top
Width108 mm
Height99.5 mm
Depth74 mm
A9Y76740 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 61009-2-1
Relative humidity95 % at 55 °C
Operating altitude2000 m
A9Y76740 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

The Schneider Electric A9Y76740 is an add-on residual current device (RCD) from the Acti9 Vigi iCG40 range, designed to bolt onto the outgoing side of a compatible Acti9 MCB via the screw terminals. It provides earth-leakage protection for a 3P+N circuit at 40 A rated current and 400 V AC operational voltage. The 300 mA sensitivity is selective (time-delayed), so it coordinates with downstream 30 mA RCDs — the upstream unit holds off during a fault to let the closer device clear first, avoiding a whole-section blackout for a single branch fault.

Rated at 40 A (In) and 400 V AC, this RCD handles the full load current of a typical sub-distribution board feeding lighting, general-purpose sockets, or small motor circuits — not a main incomer for a whole building, but a group feeder. The Type A-SI (Super Immunised) classification means it rejects nuisance tripping from pulsed DC fault currents and high-frequency leakage common in VFD-driven loads, switched-mode power supplies, and electronic ballasts. Standard Type A RCDs can false-trip on those waveforms; the A-SI variant holds steady. Voltage-independent tripping (no need for an auxiliary supply) means the RCD clears a ground fault even if the line voltage collapses — critical for safety in a group incomer where a lost neutral could otherwise leave a fault undetected.

Clip-on DIN rail mounting, 108 mm wide (6 x 9 mm pitches), with a depth of 74 mm and height of 99.5 mm. Tunnel-type terminals accept 1…16 mm² rigid or 1…10 mm² flexible cable on top; strip length 14 mm, tighten to 2 N·m. The screw connection to the upstream MCB uses the same terminals — no pigtail or flying leads. Rated for ambient operation from -25 °C to 60 °C, storage from -40 °C to 85 °C, and up to 2000 m altitude.

Frequently asked questions

What compliance standards does A9Y76740 meet?

It is designed to EN/IEC 61009-2-1 (RCCB with overcurrent protection — though this is an add-on RCD, the standard governs the residual current function). Pollution degree 3, rated impulse withstand voltage 4 kV, and IMQ quality label are listed.

MPN