Skip to main content
Schneider Electric ABE7S16S1B2E — PLC Accessories

Schneider ABE7S16S1B2E Solid State Output Relay Sub-base, 16

MPNABE7S16S1B2E
Active

Schneider Modicon ABE7 solid state output relay sub-base, ABE7S16S1B2E, 16 channels, 0.5 A per channel, 24 V DC, 125 mm wide, spring terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

ABE7S16S1B2E — I/O & Signal
ParameterValue
Number of channels16

Product details

The Schneider Modicon ABE7S16S1B2E is a solid state output relay sub-base with 16 channels, each rated at 0.5 A at the preactuator end. The sub-base provides short-circuit and overload fault protection via an internal 2 A fast-blow fuse at the PLC end, plus an adjustable external fuse at the preactuator end. Response time is ≤ 0.2 ms from state 0 to 1, making it suitable for fast-switching applications in control panels.

The 0.5 A per channel rating at the preactuator end governs the load each output can drive — stay within this for inductive or resistive loads. Maximum switching current is 700 mA for DC-12 and DC-13 loads, with a minimum switching current of 1 mA, so it handles both small signal relays and moderate solenoid valves. The maximum current per output common is 9 A, which means you can group up to 18 channels at 0.5 A each on a single common, but watch the thermal derating above 40 °C.

This sub-base is a DIN-rail-mounted component (35 mm symmetrical rail) with a width of 125 mm, so plan for that slot in your panel layout. Spring terminals accept 0.14...2.5 mm² solid or flexible wire, making field wiring straightforward. The removable terminal block simplifies replacement without disturbing wiring. IP2X protection means it's suitable for enclosed cabinets, not open washdown areas.

Frequently asked questions

What are the key ratings for this sub-base?

16 channels at 0.5 A per channel (preactuator end), 24 V DC supply, response time ≤ 0.2 ms, maximum switching current 700 mA DC-12/DC-13, and maximum current per output common of 9 A.

What protection does it offer?

Short-circuit and overload protection via an internal 2 A fast-blow fuse at the PLC end and an adjustable external fuse at the preactuator end.

How does it mount and wire?

Mounts on 35 mm symmetrical DIN rail or screws onto a solid plate. Spring terminals accept 0.14...2.5 mm² wire. The terminal block is removable.

MPN
ABE7S16S1B2E