Skip to main content
Schneider Electric ATV1200A125001010 — AC Drive (VFD) 480V

Schneider ATV1200A125001010 AC Drive, 10.45 MW, 2970-3630 V

MPNATV1200A125001010
Active

Schneider Electric Altivar 1200 series, ATV1200A125001010 medium-voltage AC drive, 10.45 MW, 2970-3630 V input, 48-pulse diode rectifier, floor-standing enclosure.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATV1200A125001010 — Identification
ParameterValue
Product typeMedium voltage variable speed drive
Device short nameATV1200
Product range / familyAltivar 1200
ATV1200A125001010 — Power & Output
ParameterValue
Motor power (kW)10450 kW
Continuous output current720 A (standard overload) 576 A (high overload)
Max. transient current864 A for 60 s
Apparent power12500 kVA
ATV1200A125001010 — Input / Supply
ParameterValue
Rated supply voltage range10 kV +/- 10 %
Input line current720 A
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for control at 220 V AC, 3 kVA Internal supply for cooling fan at 380 V AC External supply for control at 220 V AC/DC (optional) External supply for cooling fan at 380 V AC (optional)
ATV1200A125001010 — Control & Performance
ParameterValue
Output frequency range0.5...120 Hz voltage/frequency ratio (V/f) 0.5...70 Hz vector control with/without speed feedback
Asynchronous motor control modesVoltage/frequency ratio (V/f) Sensorless flux vector control Closed-loop control with encoder Vector control with sensor, optional
Synchronous motor control modesVoltage/frequency ratio (V/f) Closed-loop control with encoder
ATV1200A125001010 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated
Protection functionsGround fault protection: drive
Prospective short-circuit current (Isc)31.5 kA for 150 ms
ATV1200A125001010 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP42 IP31 IP41
Acoustic noise level80 dB
Cooling methodForced convection
Assembly / installation styleIn floor-standing enclosure with separate air flows
ATV1200A125001010 — Environmental
ParameterValue
Operating ambient temperature0...40 °C 40...50 °C (with current derating of 2 % per °C)
Operating altitude1000...2000 m with current derating 0.6 % per 100 m
Relative humidity0...90 % 0...95 % optional
Storage / transport temperature-10...60 °C
Pollution degree2 conforming to EN/IEC 61800-5-1
Vibration resistance4.9 m/s² (f= 10...50 Hz)
ATV1200A125001010 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceEN/IEC 60204-11 EN/IEC 60529 EN/IEC 61800-3 EN/IEC 61800-4 EN/IEC 61800-5-1
ATV1200A125001010 — Communication
ParameterValue
Communication protocolsHuman machine interface: Modbus with 2-wire RS485(1) - SUB-D 9 Human machine interface: Modbus TCP with (1) - RJ45 Human machine interface: EtherNet/IP with (1) - RJ45 Human machine interface: Profibus with (1) - SUB-D 9 Human machine interface: DeviceNet with (1) - SUB-D 9

Product details

The ATV1200A125001010 is a medium-voltage variable frequency drive rated for 10.45 kW motor power, supplied from a 2970–3630 V AC line via a 48-pulse diode rectifier bridge. That input configuration draws 720 A line current and presents an apparent power of 12.5 MVA — numbers that define the upstream transformer and switchgear rating, not just the drive itself. The 48-pulse topology reduces line-side harmonics to levels that typically meet IEEE 519 without additional filtering, which saves cabinet space and avoids tuning hassles on weak grids. Prospective short-circuit current withstand is 31.5 kA for 150 ms — the drive can ride through a bolted fault on its input bus long enough for the upstream breaker to clear, without self-destructing.

Floor-standing enclosure — dimensions and site prep

The drive ships in a floor-standing enclosure with separate airflows for power and control sections. Dimensions are 3040 mm high, 15080 mm wide, 1600 mm deep — this is a room-sized assembly, not a cabinet you slide into a row. The width alone dictates a dedicated drive room or a reinforced slab. Cooling is forced convection moving 140,000 m³/h of air — plan for intake and exhaust louvres sized to that flow, plus acoustic treatment given the 80 dB noise level. Electrical connection uses M10 screw-type bars accepting up to 6 x 40 mm² per phase, entry from top or bottom. The cable gland plate must accommodate that cross-section.

Lifecycle and compliance — active production, CE marked

CE marking is in place, with compliance to EN/IEC 60204-11, EN/IEC 60529, EN/IEC 61800-3 (EMC), EN/IEC 61800-4, and EN/IEC 61800-5-1 (safety). The integrated EMC filter covers conducted emissions for the drive's rating class. Pollution degree 2 per EN/IEC 61800-5-1 and overvoltage category II — suitable for controlled indoor environments with non-conductive pollution.

Frequently asked questions

What is the ATV1200A125001010 used for?

It is a medium-voltage AC drive for asynchronous motors up to 10.45 MW, typically found on large pumps, fans, compressors, and conveyors in mining, cement, water, and oil & gas installations where a 3.3 kV supply is available.

What compliance documentation comes with the ATV1200A125001010?

The drive carries CE marking and complies with EN/IEC 61800-3 (EMC), EN/IEC 61800-5-1 (safety), and EN/IEC 60204-11. An integrated EMC filter is standard. RoHS/REACH declarations are typically included with the documentation package from Schneider.

MPN
ATV1200A125001010