Specifications

Identification

ATV1200A26706363 — Identification
ParameterValue
Product typeMedium voltage variable speed drive
Device short nameATV1200
Product range / familyAltivar 1200

Power & Output

ATV1200A26706363 — Power & Output
ParameterValue
Motor power (kW)2006 kW
Continuous output current220 A (standard overload) 176 A (high overload)
Max. transient current264 A for 60 s
Apparent power2400 kVA

Input / Supply

ATV1200A26706363 — Input / Supply
ParameterValue
Rated supply voltage range6.3 kV +/- 10 %
Input line current220 A
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for control at 220 V AC, 3 kVA Internal supply for cooling fan at 380 V AC External supply for control at 220 V AC/DC (optional) External supply for cooling fan at 380 V AC (optional)

Control & Performance

ATV1200A26706363 — Control & Performance
ParameterValue
Output frequency range0.5...120 Hz voltage/frequency ratio (V/f) 0.5...70 Hz vector control with/without speed feedback
Asynchronous motor control modesClosed-loop control with encoder Vector control with sensor, optional Voltage/frequency ratio (V/f) Sensorless flux vector control
Synchronous motor control modesClosed-loop control with encoder Voltage/frequency ratio (V/f)

Protection & EMC

ATV1200A26706363 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated
Protection functionsGround fault protection: drive
Prospective short-circuit current (Isc)31.5 kA for 150 ms

Mechanical & Cooling

ATV1200A26706363 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP31 IP42 IP41
Acoustic noise level80 dB
Cooling methodForced convection
Assembly / installation styleIn floor-standing enclosure with separate air flows

Environmental

ATV1200A26706363 — Environmental
ParameterValue
Operating ambient temperature0...40 °C 40...50 °C (with current derating of 2 % per °C)
Operating altitude1000...2000 m with current derating 0.6 % per 100 m
Relative humidity0...90 % 0...95 % optional
Storage / transport temperature-10...60 °C
Pollution degree2 conforming to EN/IEC 61800-5-1
Vibration resistance4.9 m/s² (f= 10...50 Hz)

Approvals

ATV1200A26706363 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceEN/IEC 60204-11 EN/IEC 60529 EN/IEC 61800-3 EN/IEC 61800-4 EN/IEC 61800-5-1

Communication

ATV1200A26706363 — Communication
ParameterValue
Communication protocolsHuman machine interface: Modbus with 2-wire RS485(1) - SUB-D 9 Human machine interface: Modbus TCP with (1) - RJ45 Human machine interface: EtherNet/IP with (1) - RJ45 Human machine interface: Profibus with (1) - SUB-D 9 Human machine interface: DeviceNet with (1) - SUB-D 9

Product details

Floor-standing MV drive, 2006 kW, 36-pulse input

The ATV1200A26706363 is a Schneider Electric Altivar 1200 medium-voltage variable speed drive rated for 2006 kW motor power with a supply voltage range of 2970 to 3630 V. It uses a 36-pulse diode rectifier bridge on the input side, which significantly reduces line-side harmonics compared to 6- or 12-pulse topologies — a key advantage when connecting to weak grids or meeting IEEE 519 compliance without external filters. The drive is assembled in a floor-standing enclosure with separate air flows for power and control sections, and forced convection cooling moves 23,100 m³/h of air through the cabinet.

Physical footprint and installation constraints

The enclosure measures 2670 mm high by 5170 mm wide (standard efficiency) or 5470 mm wide (high efficiency), with a uniform depth of 1700 mm for both variants. Power cable entry is via M10 bar-type terminals accepting up to 6 x 40 mm² conductors per phase, with entry from the bottom or top of the cabinet.

Overload capability and protection

The drive offers two overload profiles: standard overload withstands 1.2× In for 60 s or 1.5× In for 3 s; high overload profile handles 1.5× In for 60 s or 1.85× In for 3 s. Ground fault protection is integrated at the drive level, and the prospective line short-circuit current rating is 31.5 kA for 150 ms. Dielectric strength between earth and power terminals is 20 kV AC, with overvoltage category II per EN/IEC 61800-5-1 and pollution degree 2.

Control interfaces and I/O complement

Four software-configurable analogue inputs accept 0-20 mA or 4-20 mA signals at 24 V max with 250 Ω impedance; two analogue outputs of the same type are available. Six discrete inputs are standard, expandable to ten with an optional module. Control power requires an external 220 V AC supply at 3 kVA; the cooling fan runs from a separate 380 V AC supply, with optional external supplies for both.

Standards compliance and lifecycle status

The drive carries CE marking and complies with EN/IEC 60204-11, EN/IEC 60529, EN/IEC 61800-3, EN/IEC 61800-4, and EN/IEC 61800-5-1.

MPN