Schneider Electric ATV1200A4704242 — AC Drive (VFD) 480V

Schneider Electric ATV1200A4704242 Altivar 1200, 393 kW

MPNATV1200A4704242
Active

Schneider Electric Altivar 1200 series, ATV1200A4704242 medium voltage drive, 393 kW, 470 kVA, 24-pulse rectifier, 2970-3630 V supply, floor-standing enclosure.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV1200A4704242 — Identification
ParameterValue
Product typeMedium voltage variable speed drive
Device short nameATV1200
Product range / familyAltivar 1200

Power & Output

ATV1200A4704242 — Power & Output
ParameterValue
Motor power (kW)393 kW
Continuous output current65 A (standard overload) 52 A (high overload)
Max. transient current78 A for 60 s
Apparent power470 kVA

Input / Supply

ATV1200A4704242 — Input / Supply
ParameterValue
Rated supply voltage range4.16 kV +/- 10 %
Input line current65 A
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for control at 220 V AC, 3 kVA Internal supply for cooling fan at 380 V AC External supply for control at 220 V AC/DC (optional) External supply for cooling fan at 380 V AC (optional)

Control & Performance

ATV1200A4704242 — Control & Performance
ParameterValue
Output frequency range0.5...120 Hz voltage/frequency ratio (V/f) 0.5...70 Hz vector control with/without speed feedback
Asynchronous motor control modesClosed-loop control with encoder Vector control with sensor, optional Sensorless flux vector control Voltage/frequency ratio (V/f)
Synchronous motor control modesVoltage/frequency ratio (V/f) Closed-loop control with encoder

Protection & EMC

ATV1200A4704242 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated
Protection functionsGround fault protection: drive
Prospective short-circuit current (Isc)31.5 kA for 150 ms

Mechanical & Cooling

ATV1200A4704242 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP41 IP42 IP31
Acoustic noise level80 dB
Cooling methodForced convection
Assembly / installation styleIn floor-standing enclosure with separate air flows

Environmental

ATV1200A4704242 — Environmental
ParameterValue
Operating ambient temperature0...40 °C 40...50 °C (with current derating of 2 % per °C)
Operating altitude1000...2000 m with current derating 0.6 % per 100 m
Relative humidity0...90 % 0...95 % optional
Storage / transport temperature-10...60 °C
Pollution degree2 conforming to EN/IEC 61800-5-1
Vibration resistance4.9 m/s² (f= 10...50 Hz)

Approvals

ATV1200A4704242 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceEN/IEC 60204-11 EN/IEC 60529 EN/IEC 61800-3 EN/IEC 61800-4 EN/IEC 61800-5-1

Communication

ATV1200A4704242 — Communication
ParameterValue
Communication protocolsHuman machine interface: Modbus with 2-wire RS485(1) - SUB-D 9 Human machine interface: Modbus TCP with (1) - RJ45 Human machine interface: EtherNet/IP with (1) - RJ45 Human machine interface: Profibus with (1) - SUB-D 9 Human machine interface: DeviceNet with (1) - SUB-D 9

Product details

What the 24-pulse input buys you on harmonics

The ATV1200A4704242: The 24-pulse diode rectifier bridge (cite:) cancels the 5th, 7th, 11th, and 13th harmonics at the input — you stay below IEEE 519 distortion limits without an external filter. The integrated EMC filter (cite:) handles the conducted emissions side. For a site with a weak grid or multiple drives on the same transformer, this saves the cost of a separate harmonic trap cabinet. Apparent power is 470 kVA (cite:), line current 65 A (cite:). The prospective short-circuit current rating is 31.5 kA for 150 ms (cite:) — the drive's input stage can ride through a fault on the primary side without the upstream breaker clearing first. Dielectric strength between earth and power terminals is 20 kV AC (cite:), which covers the transient overvoltages expected on a medium-voltage bus. Overload capability is specified in two duty bands: 1.2× rated current for 60 s (standard overload) or 1.5× for 3 s; the high-overload profile gives 1.5× for 60 s and 1.85× for 3 s (cite:). That second band matters if the driven load — a crusher, centrifuge, or conveyor with a high breakaway torque — needs extra current during acceleration.

Floor-standing enclosure — what fits through the door

The drive ships in a floor-standing enclosure with separate air flows for the power section and the control electronics (cite:). Standard-efficiency configuration: 1400 mm deep, 2660 mm wide, 2520 mm high (cite:,). High-efficiency option adds 100 mm to depth, 300 mm to width, and 150 mm to height. Cooling airflow is 9900 m³/h standard, 13200 m³/h high-efficiency (cite:) — plan the room ventilation around that exhaust volume. Operating altitude range is 1000-2000 m with a 0.6% current derating per 100 m above 1000 m (cite:). The 80 dB noise level (cite:) means ear protection in the drive room is mandatory — not a surprise for an MV drive, but worth flagging for the site acoustics plan.

CE marked (cite:). Designed to EN/IEC 60204-11 (safety of machinery — MV equipment), EN/IEC 60529 (enclosure protection), EN/IEC 61800-3 (EMC for adjustable-speed drives), EN/IEC 61800-4 (voltage-source drives), and EN/IEC 61800-5-1 (electrical, thermal, and energy safety) (cite:). Pollution degree 2 per EN/IEC 61800-5-1 (cite:), overvoltage category II (cite:). The compliance package covers the machinery directive and the EMC directive for industrial environments.

Frequently asked questions

How do I order the ATV1200A4704242 and get a price quote?

Sourced and quoted to order through independent industrial distribution. No stock-holding claim — each quote reflects the supply position at that moment.

MPN