800 kW in a 30-pulse topology
The Schneider Electric ATV6000C100A6666NA3 is an Altivar Process ATV6000 AC drive rated 800 kW for normal duty and 760 kW for heavy duty, with a 30-pulse diode rectifier front end that holds input current THDI below 3% per IEEE 519:1992 without external filters.
Multilevel PWM and harmonic compliance
Output uses IGBT inverter cells in a multilevel PWM topology; the 30-pulse input bridge delivers a power factor of 96% and line current draw of 87.5 A normal duty / 83 A heavy duty. Integrated EMC filter meets IEC 61800-3 category C3 on the control side and C4 on the power side, which means the drive is intended for industrial environments with a dedicated transformer or isolation — not direct connection to a public low-voltage grid without additional mitigation. Power losses are 34.9 kW at normal duty and 33.1 kW at heavy duty; the forced-convection cooling system and the 80 dB noise level should be factored into the equipment room HVAC and acoustic planning.
Floor-standing enclosure and integration
The drive ships in a floor-standing enclosure (3060 mm wide × 2617 mm high × 1400 mm deep) complete with power cells, phase-shifting transformer, cooling fans, HMI, medium voltage arrestors, and plinth — a near-turnkey power section that needs only incoming supply and motor cables at the bottom cable entry. Two option card slots (Slot A and Slot B) accept fieldbus modules (Profibus DP V1, PROFINET, DeviceNet, CANopen, EtherCAT) and encoder feedback interfaces (digital, analog, resolver, HTL), so the drive integrates into most automation architectures without a separate gateway.