Identification

ATV6000C150A1111NA3 — Identification
ParameterValue
Product typeMedium voltage variable speed drive
Device short nameATV6000
Product range / familyAltivar Process ATV6000

Power & Output

ATV6000C150A1111NA3 — Power & Output
ParameterValue
Motor power (kW)1200 kW for normal duty 1140 kW for heavy duty
Continuous output current75.3 A normal duty 72 A heavy duty
Max. transient current113 A during 3 s (normal duty) 135 A during 3 s (heavy duty)
Apparent power1500 kVA

Input / Supply

ATV6000C150A1111NA3 — Input / Supply
ParameterValue
Rated supply voltage range11 kV +/- 10 %
Input line current78.8 A normal duty 75 A heavy duty
Network number of phases3 phases
Internal/auxiliary suppliesInternal supply for digital inputs and PoE 24 V DC 21...27 V, Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, External supply for digital inputs 24 V DC 19...30 V External supply for control circuit 100...240 V AC 47...63 Hz External supply for control circuit 120...370 V DC +/- 10 % 1 kVA Auxiliary power supply 230 V AC +/- 10 % External supply for cooling fan 400 V AC +/- 10 % 7 kVA

Control & Performance

ATV6000C150A1111NA3 — Control & Performance
ParameterValue
Output frequency range0.1...120 Hz
Asynchronous motor control modesClosed loop vector control U/F vector control Energy saving control Vector control with slip compensation in open loop
Synchronous motor control modesPermanent magnet control in open loop Permanent magnet control in close loop Line start permanent magnet motor

Protection & EMC

ATV6000C150A1111NA3 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated conforming to IEC 61800-3 category C3 control Integrated conforming to IEC 61800-3 category C4 power
Protection functionsLine supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overvoltages on the DC bus: drive Thermal overload for transformer: drive Cabinet overheating: drive Overcurrent: drive Overload: drive Short-circuit protection: drive IGBT for each cell: drive Thermal protection: motor Motor phase break: motor Motor earth fault: motor Break on the control circuit: drive Fan monitoring: drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)31.5 kA for 150 ms

Mechanical & Cooling

ATV6000C150A1111NA3 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP31 conforming to IEC 60529
Acoustic noise level80 dB
Cooling methodForced convection
Assembly / installation styleIn floor-standing enclosure

Environmental

ATV6000C150A1111NA3 — Environmental
ParameterValue
Operating ambient temperature0...40 °C 40...50 °C with derating factor -25...70 °C during transport
Operating altitude1000...2000 m with derating factor
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature0...50 °C
Pollution degree2 conforming to IEC 61800-5-1

Approvals

ATV6000C150A1111NA3 — Approvals
ParameterValue
Certifications & markingEAC CE
Standards complianceIEC 61800-3 EN/IEC 61800-4 IEC 61800-5-1 IEC 60529 IEEE 519:1992 EN/IEC 60076

Communication

ATV6000C150A1111NA3 — Communication
ParameterValue
Communication protocolsEthernet IP/Modbus TCP

Product details

The Schneider ATV6000C150A1111NA3 is a medium-voltage variable speed drive from the Altivar Process ATV6000 range, rated for 1500 kVA apparent power and delivering 1200 kW on normal duty or 1140 kW on heavy duty. It drives synchronous, permanent magnet, and asynchronous motors — so it covers the common motor types in a medium-voltage installation without needing a different drive platform.

The 54-pulse diode rectifier bridge keeps input current THDI below 3% per IEEE 519-1992. Line current draws 78.8 A on normal duty and 75 A on heavy duty. Power losses run 52.2 kW normal, 49.6 kW heavy. The drive ships as a complete floor-standing enclosure with power cells, phase-shifting transformer, cooling fans, HMI, medium-voltage arrestors, and plinth — so it arrives as a functional assembly, not a stack of loose modules. The 10-inch LCD touch screen is multi-language, which cuts commissioning time if the crew isn't all English-primary.

Integration notes

Cable entry is bottom only — plan your gland plate and busway accordingly. The enclosure footprint is 4160 mm wide × 1600 mm deep × 2751 mm high; that's a substantial floor area, so confirm the substation or motor control center room can take it before you cut the opening. Noise level is 80 dB — hearing protection zone for anyone near it during operation. Two option-card slots (A and B) accept communication modules for Profibus DP V1, PROFINET, DeviceNet, CANopen, EtherCAT, plus encoder interfaces (digital, analog, resolver, HTL) and I/O or relay extensions. That covers the common fieldbuses without a gateway box. The control block also has two RJ45 for Ethernet IP/Modbus TCP and one RJ45 for Modbus serial.

Frequently asked questions

What are the key power ratings?

1500 kVA apparent power, 1200 kW normal duty / 1140 kW heavy duty motor power, with line current 78.8 A normal / 75 A heavy duty.

What physical footprint does this drive require?

The floor-standing enclosure is 4160 mm wide × 1600 mm deep × 2751 mm high.

What communication options are available?

Slot A accepts Profibus DP V1, PROFINET, DeviceNet, CANopen, or EtherCAT modules. Slot B accepts encoder interface modules. The control block has two RJ45 for Ethernet IP/Modbus TCP and one RJ45 for Modbus serial.

MPN
ATV6000C150A1111NA3