Supply and footprint
The ATV6000C742A1010NA3: The drive requires a 50 Hz supply (50 Hz +/- 5 %) and draws 340 A heavy duty or 428 A normal duty line current. Input THDI is under 3 % conforming to IEEE 519-1992, achieved by the 48-pulse rectifier. The floor-standing enclosure measures 8860 mm wide by 1800 mm deep by 3151 mm high — plan the substation bay accordingly.
Control and I/O
The control block provides 2 RJ45 ports for Ethernet IP/Modbus TCP and 1 RJ45 for Modbus serial. Slot A accepts fieldbus modules for Profibus DP V1, PROFINET, DeviceNet, CANopen (RJ45, SUB-D 9, or screw terminals), or EtherCAT. Slot B takes encoder interface modules (5/12 V digital, analog, resolver, HTL). Both slots can host digital/analog I/O extension or output relay extension modules. The 10-inch LCD touch screen multi-language display is standard.
Protection and compliance
Protection covers line supply overvoltage/undervoltage/phase loss, DC bus overvoltage, transformer thermal overload, cabinet overheating, overcurrent, overload, short-circuit, IGBT cell faults, motor thermal/phase/earth faults, control circuit break, and fan monitoring. The drive carries CE and EAC marking and conforms to IEC 61800-3, IEC 61800-4, IEC 61800-5-1, IEC 60529, IEEE 519:1992, and EN/IEC 60076. The integrated EMC filter meets IEC 61800-3 category C3 on the control side and C4 on the power side.
Provided equipment
The drive ships with plinth, medium-voltage arrestors, human-machine interface, enclosure, cooling fans, phase-shifting transformer, and power cells.