The Schneider Electric ATV6000D750A4242ND is a current-production Altivar Process ATV6000 medium-voltage drive, delivering 750 kVA apparent power with a 24-pulse diode rectifier input that keeps line THDI below 3% per IEEE 519-1992 — no external filter needed for that spec. It's rated 600 kW normal duty, 480 kW heavy duty, with a 96% power factor and an integrated EMC filter (C3 control side, C4 power). The enclosure sits at 104.7 x 99.9 x 55.1 inches and includes the phase-shifting transformer, power cells, cooling fans, HMI, and cabinet cooling.
The 600 kW normal duty / 480 kW heavy duty rating sets the continuous and overload capability — heavy duty for constant-torque loads (conveyors, extruders) and normal duty for variable-torque (pumps, fans). The 24-pulse input, combined with the phase-shifting transformer, suppresses the 5th and 7th harmonics to meet IEEE 519 without an active front end. Protection covers line over/undervoltage, phase loss, DC bus overvoltage, thermal overload on the transformer, cabinet overtemperature, output overcurrent/short-circuit, IGBT faults, motor phase/earth faults, and fan monitoring. The 10-inch LCD touchscreen provides multi-language access to diagnostics and commissioning.
Marked CULus, CE, UKCA — suitable for North American and European installations. Standards include IEC 61800-3 (EMC), IEC 61800-5-1 (safety), IEEE 519, and UL 347A. The isolation between power and control is electrical. Pollution degree 2 per IEC 61800-5-1.