Skip to main content
Schneider Electric ATV6A0C20Q6 — AC Drive (VFD) 600V

Schneider ATV6A0C20Q6 Altivar Process Drive, 200 kW

MPNATV6A0C20Q6
Active

Schneider Electric Altivar Process ATV6A0C20Q6, modular 200 kW VFD, 690 V, integrated C3 EMC filter, STO SIL 3.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATV6A0C20Q6 — Identification
ParameterValue
Product range / seriesAltivar Process ATV600
Device short name / model codeATV6A0
Product / component typeVariable speed drive
ATV6A0C20Q6 — Electrical (input)
ParameterValue
Rated supply voltage690 V - 15...10 %
Network phases3 phases
Supply frequency50...60 Hz - 5...5 %
Line (input) current200.0 A 690 V normal duty) 163.0 A 690 V heavy duty)
Prospective line short-circuit current (Isc)50 kA
EMC filterIntegrated 984.3 ft (300 m) IEC 61800-3 category C3
Max. input current THD (THDi)<48 % full load IEC 61000-3-12
ATV6A0C20Q6 — Output / Performance
ParameterValue
Apparent power239 kVA at 690 V normal duty 195 kVA at 690 V heavy duty
Continuous output current215.0 A at 2.5 kHz normal duty 175.0 A at 2.5 kHz heavy duty
Switching (PWM) frequency2...4.9 kHz adjustable with derating factor
ATV6A0C20Q6 — Communication
ParameterValue
Communication protocolsEthernet Modbus serial Modbus TCP
Address range1...247 Modbus serial
Data format8 bits, configurable odd, even or no parity Modbus serial
ATV6A0C20Q6 — Mechanical
ParameterValue
Mounting modeCabinet mount
Terminal / wiring connectionControl removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars
Product destination / compatibilitySynchronous motors Asynchronous motors
ATV6A0C20Q6 — Environmental
ParameterValue
Degree of protection (IEC, IP)UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)
IP rating (with kit options)IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529
Operating ambient temperature14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor
Storage temperature-40...158 °F (-40...70 °C)
Operating altitude (with derating)< 2000 m with current derating above 1000m
Relative humidity5...95 % without condensation IEC 60068-2-3
Pollution degree2 IEC 61800-5-1
Environmental resistance classesChemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3 Humidity resistant class 3K3 IEC 60721-3-3
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
Shock resistance4 gn 11 ms IEC 60068-2-27
Acoustic noise level69 dB 86/188/EEC
ATV6A0C20Q6 — Approvals & Compliance
ParameterValue
StandardsIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1
Agency markings / approvalsCE

Product details

What this ATV6A0C20Q6 covers

The ATV6A0C20Q6 is a Schneider Electric Altivar Process ATV600 drive rated for 200 kW at 690 V in normal duty, 160 kW in heavy duty. It handles asynchronous and synchronous motors, with line current at 200 A (normal) or 163 A (heavy). This is the modular version — separate power module and control unit shipped together with mechanical mounting kits and fuses. It means you can swap the control section without pulling the whole frame if a fieldbus card fails.

Ratings that matter on the floor

Integrated EMC filter to IEC 61800-3 category C3 saves a line reactor or external filter for most industrial environments. The drive's THDI stays under 48% at full load per IEC 61000-3-12, so it won't trash your panel distribution. Pair it with a suitable safety relay or controller. Switching frequency runs 2 to 4.9 kHz adjustable, with derating above 4 kHz. For 200 kW motor cables, keep it at 2–3 kHz unless you want to derate output current.

Mounting and wiring quick notes

Cabinet mount only — UL Type 1 or Type 12 when integrated into an enclosure. Forced convection cooling keeps the heat moving; make sure your cabinet ventilation handles the dissipation. Line and motor connections use M10 screw bars on the power module. The control section has slot A for fieldbus options (Profibus, PROFINET, DeviceNet, CANopen, Modbus TCP) and slot A/B for digital/analog I/O or relay extension. Modbus serial is on RS-485 2-wire, RTU format, 1 to 247 addresses at 4.8-38.4 kbps. Ethernet/Modbus TCP at 10/100 Mbps with half/full duplex and auto-neg. No MODBUS bridge built-in; the serial and Ethernet ports are independent.

Frequently asked questions

What is the marking on this drive?

The ATV6A0C20Q6 carries CE marking.

What variant is the ATV6A0C20Q6?

It is a modular version, meaning the power module and control unit are separate components shipped together in a kit.

MPN
ATV6A0C20Q6