Skip to main content
Schneider Electric ATV6B0C11Q4 — AC Drive (VFD) 480V

ATV6B0C11Q4 Altivar Process 110 kW, 175 A

MPNATV6B0C11Q4
Active

Schneider Altivar Process ATV600 series, ATV6B0C11Q4 modular drive, 110 kW normal duty / 90 kW heavy duty at 400 V, 175 A line current, integrated EMC filter Category C3, STO SIL3 safety.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV6B0C11Q4 — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATV6B0
Product range / familyAltivar Process ATV600

Power & Output

ATV6B0C11Q4 — Power & Output
ParameterValue
Motor power (kW)110.0 kW at 400 V normal duty 90.0 kW at 400 V heavy duty
Continuous output current211.0 A at 2.5 kHz normal duty 173.0 A at 2.5 kHz heavy duty
Max. transient current232.1 A during 60 s (normal duty) 259.5 A during 60 s (heavy duty)
Apparent power121 kVA at 400 V normal duty 100 kVA at 400 V heavy duty

Input / Supply

ATV6B0C11Q4 — Input / Supply
ParameterValue
Rated supply voltage range400 V - 15...10 %
Input line current175.0 A at 400 V (normal duty) 144.0 A at 400 V (heavy duty)
Network number of phases3 phases

Control & Performance

ATV6B0C11Q4 — Control & Performance
ParameterValue
Output frequency range0...500 Hz
Asynchronous motor control modesConstant torque standard Variable torque standard Optimized torque mode
Synchronous motor control modesPermanent magnet motor Synchronous reluctance motor

Protection & EMC

ATV6B0C11Q4 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated with 300 m conforming to IEC 61800-3 category C3
Protection functionsThermal protection: motor Safe torque off: motor Motor phase break: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)50 kA

Mechanical & Cooling

ATV6B0C11Q4 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP00 (for IP21 or IP54 cabinet integration) conforming to IEC 61800-5-1 IP00 (for IP21 or IP54 cabinet integration) conforming to IEC 60529
Acoustic noise level70 dB conforming to 86/188/EEC
Cooling methodForced convection

Environmental

ATV6B0C11Q4 — Environmental
ParameterValue
Operating ambient temperature-10...40 °C without derating 40...50 °C with derating factor
Operating altitude1000...4800 m with current derating above 1000m
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature-40...70 °C
Pollution degree2 conforming to IEC 61800-5-1
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6

Approvals

ATV6B0C11Q4 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1

Communication

ATV6B0C11Q4 — Communication
ParameterValue
Communication protocolsEthernet Modbus serial Modbus TCP

Product details

What this drive delivers for your project schedule

The ATV6B0C11Q4 is the 110 kW modular drive from the Altivar Process ATV600 family, designed to hit the motor control milestone for pumps, fans, and conveyors in your project. It's the version with the integrated EMC filter (C3) up to 300 m cable, so you can skip an external filter in many installations—saving panel space and wiring time. Rated for 175 A normal duty at 400 V, it delivers 110 kW for typical centrifugal loads; heavy duty rating is 90 kW for constant torque applications.

Cabinet mounting and cooling

Cabinet mount with forced convection cooling. At 2.5 kHz switching frequency, normal duty dissipation is 4180 W; factor that into your cabinet cooling budget. The drive accepts a communication module in Slot A—choose Profibus DP, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen to match your automation backbone. Slot A and Slot B also accept digital/analog I/O extension or output relay modules. Line-side connection is via screw terminals; motor connection uses M10 bars. Control wiring uses removable screw terminals accepting 0.5–1.5 mm² / AWG 20–16. Keep the switching frequency adjustable between 2 and 8 kHz with derating factor. STO SIL 3 safety function is built in, so you can wire the safety relay directly without an external safety module. It also includes thermal protection for motor and drive, overcurrent, overvoltage, undervoltage, phase loss, and overspeed protection.

Standards compliance and spares planning

For project procurement, this drive is available now against an RFQ. Plan a spare control module for startup—same communication card slot keeps commissioning spare ready. The integrated EMC filter (C3) with 300 m cable capability reduces external filter count and panel complexity.

Frequently asked questions

What compliance standards does the ATV6B0C11Q4 meet?

It complies with IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and ISO 13849-1. It carries CE marking.

What is the integrated EMC filter rating?

The drive has an integrated EMC filter conforming to IEC 61800-3 category C3, suitable for 300 m cable runs.

MPN
ATV6B0C11Q4