Schneider Electric ATV6B0C35T4 — AC Drive (VFD) 480V

Schneider ATV6B0C35T4 AC Drive 480V, 550 HP ND, 450 HP HD

MPNATV6B0C35T4
Active

Schneider Electric Altivar Process ATV600 series, ATV6B0C35T4 modular AC drive, 480 V, 550 HP normal duty / 450 HP heavy duty, 443 kVA, cabinet mount, integrated EMC filter C3, STO SIL 3.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV6B0C35T4 — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATV6B0
Product range / familyAltivar Process ATV600

Power & Output

ATV6B0C35T4 — Power & Output
ParameterValue
Motor power (kW)355.0 kW at 480 V normal duty 280.0 kW at 480 V heavy duty
Continuous output current660.0 A at 2.5 kHz normal duty 520.0 A at 2.5 kHz heavy duty
Max. transient current726 A 60 s normal duty) 780 A 60 s heavy duty)
Apparent power443 kVA at 480 V normal duty 362 kVA at 480 V heavy duty

Input / Supply

ATV6B0C35T4 — Input / Supply
ParameterValue
Rated supply voltage range480 V - 10...10 %
Input line current533.0 A 480 V normal duty) 436.0 A 480 V heavy duty)
Network number of phases3 phases

Control & Performance

ATV6B0C35T4 — Control & Performance
ParameterValue
Output frequency range0...500 Hz
Asynchronous motor control modesConstant torque standard Variable torque standard Optimized torque mode
Synchronous motor control modesPermanent magnet motor Synchronous reluctance motor

Protection & EMC

ATV6B0C35T4 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated 984.3 ft (300 m) IEC 61800-3 category C3
Protection functionsThermal protection motor Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)50 kA

Mechanical & Cooling

ATV6B0C35T4 — Mechanical & Cooling
ParameterValue
Degree of protection (IP)UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)
IP degree of protectionIP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529
Acoustic noise level75 dB 86/188/EEC
Cooling methodForced convection

Environmental

ATV6B0C35T4 — Environmental
ParameterValue
Operating ambient temperature14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor
Operating altitude1000...4800 m with current derating above 1000m
Relative humidity5...95 % without condensation IEC 60068-2-3
Storage / transport temperature-40...158 °F (-40...70 °C)
Pollution degree2 IEC 61800-5-1
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6

Approvals

ATV6B0C35T4 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1

Communication

ATV6B0C35T4 — Communication
ParameterValue
Communication protocolsEthernet Modbus serial Modbus TCP

Product details

Motor sizing: the ND vs HD split decides your real load

The ATV6B0C35T4 carries two distinct ratings: 550 HP at 480 V in normal duty and 450 HP at 480 V in heavy duty, with corresponding apparent power of 443 kVA ND and 362 kVA HD. Heavy duty typically applies to constant-torque loads like conveyors or extruders; normal duty suits variable-torque fans and pumps where the headroom isn't needed. Line current at 480 V is 533 A for normal duty and 436 A for heavy duty. The switching frequency is adjustable from 2 to 8 kHz, but above 2.5 kHz a derating factor applies — if you need quieter motor operation at higher carrier frequencies, the output current ceiling drops proportionally. Prospective line short-circuit current (SCCR) is 50 kA. That is high enough for most industrial mains, but the upstream breaker must be coordinated to keep the drive protected — check the selective coordination tables in the installation manual.

Fieldbus and control: what ships on the base unit

The drive includes a Modbus serial port (2-wire RS-485, RTU frame, 1-247 addresses) and a Modbus TCP/Ethernet port (10/100 Mbit/s, half/full duplex, auto-negotiation). Slot A accepts optional communication modules for Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen (daisy chain RJ45, SUB-D 9, or screw terminals). The data format on Modbus serial is 8 bits with configurable odd, even, or no parity. For Ethernet/IP, the transmission rate is 10/100 Mbit/s — no speed negotiation issues with modern switches.

Safety and protection: STO SIL 3 and the protection map

That means the drive can be used in safety circuits up to SIL 3 without external contactors for the torque removal function — the drive's own power stage is the isolating element. The protection suite covers both motor and drive sides: thermal protection, motor phase break, overcurrent between output phases and earth, short-circuit protection, overvoltage on the DC bus, line supply over/undervoltage, line phase loss, and overspeed. For the motor, it also includes thermal protection and phase break detection.

Environmental limits and installation constraints

Operating altitude is 1000 to 4800 m with current derating above 1000 m — at 2000 m expect roughly a 10% output current reduction. The drive is cabinet mount only (UL Type 1 or Type 12 per UL 61800-5-1 when integrated into an enclosure). Vibration resistance is 1.5 mm peak-to-peak from 2 to 13 Hz and 0.5 gn from 13 to 200 Hz per IEC 60068-2-6. Shock resistance is 4 gn for 11 ms per IEC 60068-2-27. Relative humidity range is 5 to 95% without condensation per IEC 60068-2-3. The integrated EMC filter covers 300 m of motor cable per IEC 61800-3 category C3 — that is the second environment (industrial mains). For first-environment (residential) installations, an external filter may be needed.

Lifecycle and sourcing: active, modular, quoted to order

The kit composition includes: 1 control unit, mechanical mounting kits, power connection set, set of fuses, 1 power module (160 kW), and 1 front cover. Marking is CE, confirming conformity with EU directives. Standards compliance includes IEC 61800-3 (EMC), IEC 61800-5-1 (safety), IEC 61000-3-12 (harmonic limits), IEC 60721-3 (environmental conditions), IEC 61508 and IEC 13849-1 (functional safety).

Frequently asked questions

What is the difference between normal duty and heavy duty ratings on ATV6B0C35T4?

Normal duty is 550 HP at 480 V with 533 A line current and 443 kVA apparent power; heavy duty is 450 HP at 480 V with 436 A line current and 362 kVA. Heavy duty applies to constant-torque loads where the drive must deliver full torque at low speed; normal duty suits variable-torque loads like pumps and fans.

What fieldbus options are available for ATV6B0C35T4?

The base unit includes Modbus serial (RS-485, RTU) and Modbus TCP/Ethernet. Slot A accepts optional modules for Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen (three connector variants). Slots A and B also accept digital/analog I/O extension and output relay modules.