Skip to main content
Schneider Electric ATV9A0C50T6 — AC Drive (VFD) 600V

Schneider ATV9A0C50T6 ATV900 Drive, 550 hp, 600 V

MPNATV9A0C50T6
Active

Schneider Electric Altivar Process ATV900, Modular version, 550 hp at 600 V normal duty, integrated EMC filter category C3, Safe Torque Off SIL 3, dual protocol Ethernet and serial Modbus.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATV9A0C50T6 — Identification
ParameterValue
Product range / seriesAltivar Process ATV900
Device short name / model codeATV9A0
Product / component typeVariable speed drive
ATV9A0C50T6 — Electrical (input)
ParameterValue
Rated supply voltage600 V - 10...15 %
Network phases3 phases
Supply frequency50...60 Hz +/- 5 %
Line (input) current464.0 A 600 V normal duty) 383.0 A 600 V heavy duty)
Prospective line short-circuit current (Isc)50 kA
EMC filterIntegrated 984.3 ft (300 m) IEC 61800-3 category C3
Max. input current THD (THDi)<48 % from 80...100 % of load
ATV9A0C50T6 — Output / Performance
ParameterValue
Apparent power482.0 kVA at 600 V normal duty 398.0 kVA at 600 V heavy duty
Continuous output current520.0 A at 2.5 kHz normal duty 425.0 A at 2.5 kHz heavy duty
Switching (PWM) frequency2...4.9 kHz adjustable with derating factor
ATV9A0C50T6 — Communication
ParameterValue
Communication protocolsEtherNet/IP Modbus serial Modbus TCP
Address range1...247 Modbus serial
Data format8 bits, configurable odd, even or no parity Modbus serial
ATV9A0C50T6 — Mechanical
ParameterValue
Mounting modeCabinet mount
Terminal / wiring connectionControl removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars
Product destination / compatibilitySynchronous motors Asynchronous motors
ATV9A0C50T6 — Environmental
ParameterValue
Degree of protection (IEC, IP)UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)
IP rating (with kit options)IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529
Operating ambient temperature23...104 °F (-5...40 °C) without derating 104...122 °F (40...50 °C) with derating factor
Storage temperature-40...158 °F (-40...70 °C)
Operating altitude (with derating)0...2000 m with current derating above 1000m
Relative humidity5...95 % without condensation IEC 60068-2-3
Pollution degree2 IEC 61800-5-1
Environmental resistance classesChemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
Shock resistance4 gn 11 ms IEC 60068-2-27
Acoustic noise level71 dB 86/188/EEC
ATV9A0C50T6 — Approvals & Compliance
ParameterValue
StandardsIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 UL 61800-5-1
Agency markings / approvalsCE

Product details

The ATV9A0C50T6: Cabinet-mount Altivar Process ATV900 rated 550 hp at 600 V normal duty (464 A line current) and 450 hp heavy duty (383 A). Switching frequency adjustable 2–4.9 kHz with derating; suits standard induction and synchronous motors. Integrated EMC filter rated for 984.3 ft (300 m) cable at IEC 61800-3 category C3 level – no external filter needed for most industrial environments. Safe Torque Off SIL 3 included on the control board; break on the control circuit drive protection covers the loop.

Current production – no end-of-life notice. Standard lead times apply; RFQ for firm pricing and availability. CE marked, complies with IEC 61800-5-1, UL 61800-5-1, IEC 61508, and IEC 13849-1 for functional safety. Pollution degree 2 per IEC 61800-5-1. Documentation pack includes declaration of conformity for CE/UKCA; RoHS/REACH declarations available on request.

Control and supply wiring

Digital inputs powered from an external 24 V DC supply (19–30 V); a separate 24 V feed (21–27 V) runs the STO logic. Internal 10.5 V DC ±5% reference for a 1–10 kΩ potentiometer. Control terminals are removable screw, 0.5–1.5 mm² (AWG 20–16). Motor connection via M10 bars. Forced convection cooling; cabinet must provide IP21 or IP54 via the enclosure. UL type 1/12 when integrated.

Fieldbus and options

Comes standard with dual Ethernet (Modbus TCP / EtherNet/IP) at 10/100 Mbit/s and a two-wire RS-485 Modbus serial link (RTU frame, 1–247 addresses). Slot A accepts Profibus DP V1, PROFINET, DeviceNet, EtherCAT, or CANopen (RJ45, SUB-D 9, or screw terminals). Slots B and C accept I/O or relay extensions. Line current at 600 V: 464 A normal duty, 383 A heavy duty. Prospective short-circuit current 50 kA.

Frequently asked questions

What are the supply voltage requirements for the control circuits?

Digital inputs need an external 24 V DC (19–30 V). STO logic requires a separate 24 V DC (21–27 V). A 10.5 V DC ±5% reference is provided for a 1–10 kΩ potentiometer.

What compliance markings and standards does this drive carry?

It carries CE marking and complies with IEC 61800-5-1, UL 61800-5-1, IEC 61508, IEC 13849-1, and pollution degree 2. Safety function STO SIL 3 is built in.

What motor types can the ATV9A0C50T6 control?

It is rated for both synchronous and asynchronous motors, covering induction and permanent magnet machines.

MPN