Skip to main content
Schneider Electric ATV9A0M12N6 — AC Drive (VFD) 600V

Schneider ATV9A0M12N6 Altivar Process ATV900, 800 kW

MPNATV9A0M12N6
Active

Schneider Altivar Process ATV900 modular drive, ATV9A0M12N6, 800 kW at 600 V normal duty, heavy duty 710 kW, integrated EMC Category C3 filter, STO SIL3.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATV9A0M12N6 — Identification
ParameterValue
Product range / seriesAltivar Process ATV900
Device short name / model codeATV9A0
Product / component typeVariable speed drive
ATV9A0M12N6 — Electrical (input)
ParameterValue
Rated supply voltage500 V - 10...15 %
Network phases3 phases
Supply frequency50...60 Hz +/- 5 %
Line (input) current1070.0 A 600 V normal duty) 954.0 A 600 V heavy duty)
Prospective line short-circuit current (Isc)50 kA
EMC filterIntegrated 984.3 ft (300 m) IEC 61800-3 category C3
Max. input current THD (THDi)<48 % from 80...100 % of load
ATV9A0M12N6 — Output / Performance
ParameterValue
Apparent power927.0 kVA at 600 V normal duty 826.0 kVA at 600 V heavy duty
Continuous output current1230.0 A at 2.5 kHz normal duty 1030.0 A at 2.5 kHz heavy duty
Switching (PWM) frequency2...4.9 kHz adjustable with derating factor
ATV9A0M12N6 — Communication
ParameterValue
Communication protocolsEtherNet/IP Modbus serial Modbus TCP
Address range1...247 Modbus serial
Data format8 bits, configurable odd, even or no parity Modbus serial
ATV9A0M12N6 — Mechanical
ParameterValue
Mounting modeCabinet mount
Terminal / wiring connectionControl removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars
Product destination / compatibilitySynchronous motors Asynchronous motors
ATV9A0M12N6 — Environmental
ParameterValue
Degree of protection (IEC, IP)UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)
IP rating (with kit options)IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529
Operating ambient temperature23...104 °F (-5...40 °C) without derating 104...122 °F (40...50 °C) with derating factor
Storage temperature-40...158 °F (-40...70 °C)
Operating altitude (with derating)0...2000 m with current derating above 1000m
Relative humidity5...95 % without condensation IEC 60068-2-3
Pollution degree2 IEC 61800-5-1
Environmental resistance classesChemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
Shock resistance4 gn 11 ms IEC 60068-2-27
Acoustic noise level75 dB 86/188/EEC
ATV9A0M12N6 — Approvals & Compliance
ParameterValue
StandardsIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 UL 61800-5-1
Agency markings / approvalsCE

Product details

The ATV9A0M12N6 is an active-production Altivar Process ATV900 drive rated for 800 kW at 600 V normal duty (710 kW heavy duty). It drives synchronous or asynchronous motors and ships as a modular version: control unit, power module, mounting kit, fuses, and front cover. The integrated EMC filter meets Category C3 for cable runs up to 984.3 ft (300 m) — no external filter needed for most industrial installations. That eliminates the external safety relay and simplifies wiring for emergency-stop circuits that need to hold takt time without added latency.

This is a current-production unit (lifecycle stage: current). It carries CE marking and complies with IEC 61800-3 (EMC), IEC 61800-5-1 (safety), IEC 61000-3-12 (harmonics), IEC 60721-3 (environmental conditions), IEC 61508 / IEC 13849-1 (functional safety), and UL 61800-5-1. No last-time-buy or obsolescence watch needed for new designs or spares. Prospective line short-circuit current is rated 50 kA, so the drive handles high-fault-capacity panels without external current-limiting fuses in most distributions.

Integration notes

Cabinet-mount design, IP00 enclosure intended for integration into IP21 or IP54 cabinets. Cooling is forced convection — plan for airflow clearance around the power module. Line-side connection uses M10 screw terminals; motor connections via M10 bars. Control wiring uses removable screw terminals accepting 0.5–1.5 mm² (AWG 20–16). Communication flexibility: on-board Modbus serial RS-485 (2-wire, RTU frame) and Ethernet IP/Modbus TCP at 10/100 Mbit/s. Slot A accepts plug-in modules for Profibus DP V1, PROFINET, DeviceNet, EtherCAT, or CANopen (RJ45, SUB-D 9, or screw terminals). Slots A, B, and C also support digital/analog I/O and relay extension modules. Switching frequency is adjustable from 2 to 4.9 kHz with derating factor; fine for pump, fan, conveyor and general motor control. THDI stays below 48 % from 80 to 100 % load.

Frequently asked questions

What are the key electrical ratings of this drive?

Motor power: 800 kW normal duty, 710 kW heavy duty at 600 V. Line current: 1070 A normal duty, 954 A heavy duty. Apparent power: 927 kVA normal duty, 826 kVA heavy duty. Switching frequency adjustable 2–4.9 kHz.

What approvals does this drive carry?

CE marked. Complies with IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, IEC 13849-1, and UL 61800-5-1.

What are the supply voltage requirements for the control?

External 24 V DC (19–30 V) for digital inputs; internal 10.5 V DC ±5 % for a 1–10 kΩ reference potentiometer; internal 24 V DC (21–27 V) for digital inputs and STO circuit.

MPN
ATV9A0M12N6