Skip to main content
Schneider Electric ATV9B0C25T6 — AC Drive (VFD) 600V

Schneider ATV9B0C25T6 Altivar Process ATV900 Drive, 250 HP a

MPNATV9B0C25T6
Active

Schneider Electric Altivar Process ATV900, modular VFD, ATV9B0C25T6, 250 hp at 600 V normal duty, 200 hp heavy duty, STO SIL 3.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATV9B0C25T6 — Identification
ParameterValue
Product range / seriesAltivar Process ATV900
Device short name / model codeATV9B0
Product / component typeVariable speed drive
ATV9B0C25T6 — Electrical (input)
ParameterValue
Rated supply voltage600 V - 10...15 %
Network phases3 phases
Supply frequency50...60 Hz +/- 5 %
Line (input) current199.0 A 600 V normal duty) 160.0 A 600 V heavy duty) 162.0 A 600 V regenerative mode normal duty) 129.0 A 600 V regenerative mode heavy duty)
Prospective line short-circuit current (Isc)50 kA
EMC filterIntegrated 984.3 ft (300 m) IEC 61800-3 category C3
Max. input current THD (THDi)<5 % full load IEEE 519
ATV9B0C25T6 — Output / Performance
ParameterValue
Apparent power207.0 kVA at 600 V normal duty 166.0 kVA at 600 V heavy duty 169.0 kVA at 600 V normal duty regenerative mode 134.0 kVA at 600 V heavy duty regenerative mode
Continuous output current275.0 A at 2.5 kHz normal duty 215.0 A at 2.5 kHz heavy duty 275.0 A at 2.5 kHz normal duty regenerative mode 215.0 A at 2.5 kHz heavy duty regenerative mode
Switching (PWM) frequency2...4.9 kHz adjustable with derating factor
ATV9B0C25T6 — Communication
ParameterValue
Communication protocolsEtherNet/IP Modbus serial Modbus TCP
Address range1...247 Modbus serial
Data format8 bits, configurable odd, even or no parity Modbus serial
ATV9B0C25T6 — Mechanical
ParameterValue
Mounting modeCabinet mount
Terminal / wiring connectionControl removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars
Product destination / compatibilitySynchronous motors Asynchronous motors
ATV9B0C25T6 — Environmental
ParameterValue
Degree of protection (IEC, IP)UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)
IP rating (with kit options)IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529
Operating ambient temperature23...104 °F (-5...40 °C) without derating 104...122 °F (40...50 °C) with derating factor
Storage temperature-40...158 °F (-40...70 °C)
Operating altitude (with derating)0...2000 m with current derating above 1000m
Relative humidity5...95 % without condensation IEC 60068-2-3
Pollution degree2 IEC 61800-5-1
Environmental resistance classesChemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
Shock resistance4 gn 11 ms IEC 60068-2-27
Acoustic noise level73 dB 86/188/EEC
ATV9B0C25T6 — Approvals & Compliance
ParameterValue
StandardsIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 UL 61800-5-1
Agency markings / approvalsCE

Product details

Drive ratings and duty selection

The ATV9B0C25T6 is a modular Altivar Process ATV900 drive sized for 250 hp at 600 V normal duty and 200 hp at 600 V heavy duty. Line current at 600 V runs 199 A normal duty, 160 A heavy duty, with regenerative-mode ratings of 162 A and 129 A respectively. Apparent power follows: 207 kVA normal, 166 kVA heavy.

Control supply and safety

Digital inputs and STO take a 24 V DC supply (21...27 V). There is a separate 10.5 V DC reference output for a 1 to 10 kOhm potentiometer, and the external digital input supply is 24 V DC (19...30 V). The STO function is rated SIL 3 — that is a certified safe torque off, not just a software inhibit. If you are wiring a safety relay or PLC safety output, the 24 V DC STO supply must be kept separate from the control logic supply to maintain isolation.

Fieldbus and I/O options

Slot A accepts communication modules for Profibus DP V1, PROFINET, DeviceNet, CANopen (RJ45, SUB-D 9, or screw terminals), or EtherCAT. Slots A, B, and C also take digital/analog I/O extension modules and output relay extension modules. Slot B handles encoder interfaces (5/12 V digital, analog, or resolver). The drive ships with dual RJ45 Ethernet IP/Modbus TCP ports and one RJ45 Modbus serial port; Modbus serial runs RTU at 4.8 to 38.4 kbit/s, 8-bit configurable parity. For a new line, pick the fieldbus card early — the slot assignment determines which options coexist.

EMC and environment

Integrated EMC filter meets IEC 61800-3 category C3 for 300 m cable runs. The drive is cabinet-mount only, rated IP00 for integration into IP21 or IP54 enclosures. Operating altitude is 0 to 2000 m with derating above 1000 m; ambient humidity 5 to 95% non-condensing. Switching frequency is adjustable 2 to 4.9 kHz with derating — lower switching frequency reduces heat and extends cable length, higher reduces motor noise.

Frequently asked questions

What are the key ratings for the ATV9B0C25T6?

It is rated 250 hp at 600 V normal duty, 200 hp at 600 V heavy duty, with line currents of 199 A and 160 A respectively. Apparent power is 207 kVA normal duty, 166 kVA heavy duty.

What safety functions does the ATV9B0C25T6 support?

It includes STO (safe torque off) rated SIL 3.

What fieldbus options are available for the ATV9B0C25T6?

Slot A accepts Profibus DP V1, PROFINET, DeviceNet, CANopen (RJ45, SUB-D 9, or screw terminals), or EtherCAT communication modules.

MPN
ATV9B0C25T6