Skip to main content
Schneider Electric C100N460FM

C100N460FM ComPacT NS Circuit Breaker, 1000 A, 85 kA Icu

MPN C100N460FM
Active

Schneider Electric ComPacT NS new generation, C100N460FM, 4P fixed circuit breaker, 1000 A, MicroLogic 6.0 electronic trip unit, 85 kA Icu at 240 V AC, 50 kA at 415 V AC, EN/IEC 60947-2.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C100N460FM key specifications
ParameterValue
Control typeManually operated
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Utilization categoryCategory B
IP ratingIP40
Terminal pitch70 mm
Connection surface topFront
Connection surface bottomFront

All specifications

C100N460FM additional specifications
ParameterValue
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degree3 conforming to IEC 60947
Depth147 mm
Width280 mm
Height327 mm
Electrical life cycles2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2
Mechanical life cycles10000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The C100N460FM is a Schneider Electric ComPacT NS new generation 4-pole fixed circuit breaker, rated 1000 A at 50 °C, with a MicroLogic 6.0 electronic trip unit providing L (long-time overload), S (short-time short-circuit), I (instantaneous), and G (ground-fault) protection. The 85 kA Icu at 240 V AC and 50 kA at 415 V AC mean this breaker can safely interrupt fault currents up to those levels without upstream coordination failure; the N breaking capacity code (50 kA at 415 V) tells you it's rated for high-fault industrial networks. The 1000 A frame and trip unit are matched, so you don't need to oversize the breaker for the load — it's already sized for a 1000 A feeder or main.

Trip unit and protection logic

MicroLogic 6.0 is an electronic trip unit with a 20-minute thermal memory. That memory means the breaker remembers prior heating from overloads and shortens the trip time on a repeated event — important for motor or transformer feeders where inrush can mask a developing fault. The L, S, I, G protection curves are adjustable via the trip unit's dials, giving you selectivity coordination downstream. No integral earth-leakage protection is included; if you need that, you add an external Vigi module.

Fixed mounting on a backplate, with front connections both upside and downside. Neutral is on the left. Dimensions: 280 mm wide, 327 mm high, 147 mm deep. IK07 impact rating handles accidental tool strikes during installation.

Local signalling and diagnostics

Four red LEDs for fault indication (trip cause) and one yellow LED for overload pre-alarm. That saves time on troubleshooting — you can read the trip history without plugging in a laptop. The manually operated control type means no motor operator is built in; add one externally if remote switching is needed.

MPN