Schneider Electric C1047E040 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric C1047E040 MicroLogic 7.2 E Trip Unit, 40

MPNC1047E040
Obsolete

Schneider Electric ComPacT NSX series, MicroLogic 7.2 E electronic trip unit, 40 A at 40 °C, 4 poles, LSIR protection with integrated earth leakage, EN/IEC 60947-2.

$1,241.34 – $1,377.05Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C1047E040 — Residual Current Protection
ParameterValue
Earth-leakage protection class / typeClass A
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C1047E040 — Electrical Ratings
ParameterValue
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
C1047E040 — Identification
ParameterValue
Product / component typeTrip unit
Product range / familyComPacT
C1047E040 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-1
C1047E040 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

Trip unit for ComPacT NSX — MicroLogic 7.2 E

The Schneider Electric C1047E040 is a MicroLogic 7.2 E electronic trip unit for the ComPacT NSX100...250 range. It's rated 40 A at 40 °C (Ir adjustable 18–40 A) and carries LSIR protection — long-time, short-time, instantaneous, and residual earth-leakage — all integrated into one 4-pole unit. The LCD display gives you local readout of metered values, event logs, and protection settings without needing a connected gateway. Built to EN/IEC 60947-2, this trip unit is designed for distribution boards where you need coordinated protection and energy metering in one package. The 20-minute thermal memory before and after tripping means the unit remembers the thermal state of the conductors even after a short interruption — useful when re-energizing a circuit that just tripped on overload.

L (long-time) protects against sustained overloads — Ir adjustable 18–40 A with tr delay from 15 s to 400 s at 1.5×Ir. S (short-time) handles bolted faults up to the Isd setting, with delay adjustable 0–0.4 s (I²t on or off). I (instantaneous) catches high-magnitude faults with no intentional delay. R (residual) is the integrated earth-leakage protection, Class A, switchable via the IΔn rotary. That means one trip unit covers overcurrent, short-circuit, and ground-fault protection without an external module. The 4P configuration supports multiple neutral protection modes: 3D + N/2 (half-rated neutral), 4D (full-rated), 3D + OSN (oversized neutral), or no neutral protection. Neutral position is left, fixed-mount only.

Integration notes

The trip unit snaps into the ComPacT NSX100–250 fixed-mount breaker. The LCD display and local signalling LEDs (green ready, red overload at 105% Ir, orange pre-alarm at 90% Ir) give you status at a glance without opening the door.

Frequently asked questions

Where can I buy C1047E040 and get a price?

The C1047E040 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the closest alternative to C1047E040 in the ComPacT family?

Within the ComPacT NSX range, the closest functional equivalent would be another MicroLogic 7.2 E trip unit at a different amp rating — the key difference is the Ir adjustment range. For a 40 A application, the C1047E040 is the correct order code; a different rating (e.g., 25 A or 63 A) would use a different C1047Exxx variant. There is no pin-compatible drop-in from another manufacturer — the trip unit is specific to the ComPacT NSX platform.

What standards does C1047E040 comply with?

The C1047E040 complies with EN/IEC 60947-2 for low-voltage switchgear and controlgear. Pollution degree 3 per IEC 60947-1, IP40 per IEC 60529, and Class II electrical shock protection.

What compliance documentation is available for C1047E040?

As a current-production Schneider Electric product, the C1047E040 carries the manufacturer's standard declarations of conformity for the applicable EU directives (CE marking) and is designed to meet RoHS and REACH requirements. Specific documentation (declaration of conformity, material data sheets) is available on request as part of the RFQ process.

MPN