Skip to main content
Schneider Electric C10F2TM100 — Miniature Circuit Breakers (MCB)

Schneider Electric C10F2TM100 ComPacT NSX100F 100A 2P MCCB,

MPNC10F2TM100
Active

Schneider Electric ComPacT NSX, NSX100F, circuit breaker, 100 A, 2P, thermal-magnetic TM-D trip unit, 18 kA Icu at 415 V AC, toggle control.

$175.68 – $196.72Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C10F2TM100 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10F2TM100 — Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Poles configuration2P
Breaking capacity36 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380/415 V AC 50/60 Hz 1P conforming to IEC 60947-2 15 kA Icu at 440 V AC 50/60 Hz 1P conforming to IEC 60947-2 10 kA Icu at 500/525 V AC 50/60 Hz 2P conforming to IEC 60947-2 5 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 250 V DC 50/60 Hz 1 pole conforming to IEC 60947-2 36 kA Icu at 500 V DC 50/60 Hz 2 poles in series conforming to IEC 60947-2
Rated service breaking capacity (Ics)36 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 250 V DC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V DC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz 500 V DC
Rated insulation voltage (Ui)750 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10F2TM100 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 277 V In/2 10000 cycles at 277 V In
Mechanical durability (cycles)20000 cycles
C10F2TM100 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10F2TM100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10F2TM100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10F2TM100 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range1 x In
Trip unit protection functionsLI

Product details

Breaking capacity and selectivity — what the ratings mean

The C10F2TM100: The F breaking capacity code means 18 kA Icu at 380/415 V AC, 1-pole tested per IEC 60947-2. The thermal-magnetic TM-D trip provides fixed L (overload) and I (short-circuit) protection curves — no interchangeable rating plugs, so the 100 A frame is the setting.

Mounting and integration into a panel

Fixed-mount on a backplate, with front-facing line and load terminals. The 70 mm width and 161 mm height fit standard distribution panel cutouts; depth is 86 mm including the toggle. IP40 front face, IK07 impact resistance.

Frequently asked questions

What is the breaking capacity of C10F2TM100 at 415 V?

18 kA Icu at 380/415 V AC, 1-pole, per IEC 60947-2. For a 2-pole device on a 415 V line-to-line system, that is the rated ultimate short-circuit breaking capacity.

What compliance standards does C10F2TM100 meet?

It is certified to EN/IEC 60947-2, with suitability for isolation per that standard. Pollution degree 3 per IEC 60664-1, IP40 per IEC 60529, IK07 per IEC 62262.

Where can I buy C10F2TM100 and how is it quoted?

The part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock or price figures are published here.

MPN