Breaking capacity and selectivity — what the ratings mean
The C10F2TM100: The F breaking capacity code means 18 kA Icu at 380/415 V AC, 1-pole tested per IEC 60947-2. The thermal-magnetic TM-D trip provides fixed L (overload) and I (short-circuit) protection curves — no interchangeable rating plugs, so the 100 A frame is the setting.
Mounting and integration into a panel
Fixed-mount on a backplate, with front-facing line and load terminals. The 70 mm width and 161 mm height fit standard distribution panel cutouts; depth is 86 mm including the toggle. IP40 front face, IK07 impact resistance.