Skip to main content
Schneider Electric C10N3MA050 — Miniature Circuit Breakers (MCB)

Schneider Electric C10N3MA050 ComPacT NSX 50A MCCB, 3P, 90kA

MPNC10N3MA050
Active

Schneider Electric ComPacT NSX, NSX100N frame, 50 A magnetic-only MA trip unit, 3-pole, 90 kA Icu at 240 V AC, EN/IEC 60947-2.

$216.93 – $490.54Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C10N3MA050 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationMotor protection
C10N3MA050 — Ratings
ParameterValue
Rated current (In)50 A at 65 °C
Poles configuration3P
Breaking capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 50 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10N3MA050 — Protection
ParameterValue
Trip unit technologyMagnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10N3MA050 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10N3MA050 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10N3MA050 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10N3MA050 — Specifications
ParameterValue
Trip unit protection functionsI

Product details

ComPacT NSX 50 A MCCB — magnetic-only motor protection

It is designed specifically for motor protection, providing short-circuit (magnetic) protection only — no thermal overload element, so a separate motor starter or overload relay handles the thermal curve. The 50 A rating holds at 65 °C ambient, which is the standard temperature for panel derating; no further temperature correction is needed up to that point. Breaking capacity follows the N class: 90 kA Icu at 240 V AC, 50 kA at 480 V AC, and 10 kA at 600 V AC per UL 60947-4-1; IEC 60947-2 ratings run 50 kA at 415 V, 36 kA at 500 V, and 10 kA at 690 V. The IEC utilisation category is A — not intended for selectivity with downstream breakers on the same fault, but fine for radial motor feeds where coordination is handled upstream.

Mounting, dimensions, and environment

Mounts on a backplate — no DIN-rail adapter, so plan for drilled panel or a sub-plate. Dimensions are 161 mm H × 105 mm W × 86 mm D, with a 35 mm connection pitch between poles. Operating altitude 0–2000 m without derating, 2000–5000 m with derating — no issue for most plant-floor installations.

Frequently asked questions

Where can I buy C10N3MA050 and how do I get a price?

The C10N3MA050 is sourced to order against an RFQ through independent distribution. Submit a request for quotation (RFQ) to confirm availability and current pricing.

What is C10N3MA050's breaking capacity at 480 V AC?

Per UL 60947-4-1, the C10N3MA050 delivers 50 kA Icu at 480 V AC. Under IEC 60947-2, it provides 50 kA at 415 V AC and 36 kA at 500 V AC.

What compliance standards does C10N3MA050 meet?

The C10N3MA050 is certified to EN/IEC 60947-2 and UL 60947-4-1. It is suitable for isolation per EN/IEC 60947-2 and carries IP40 / IK07 protection degrees.

MPN
C10N3MA050