Schneider Electric C10N3TM100C — Miniature Circuit Breakers (MCB)

Schneider Electric C10N3TM100C ComPacT NSX100N, 100 A, 3P, T

MPNC10N3TM100C
Active

Schneider Electric ComPacT NSX, circuit breaker, 100 A, 3P, TM-D trip unit, 50 kA Icu at 415 V AC, IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10N3TM100C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10N3TM100C — Ratings
ParameterValue
Rated current (In)100 A at 50 °C
Poles configuration3P
Breaking capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10N3TM100C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10N3TM100C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10N3TM100C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10N3TM100C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10N3TM100C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The 3-pole (3P) configuration covers three-phase distribution, and the IP40 enclosure rating means it's fine in a clean indoor panel but not in a washdown area.

Mounts on a backplate in any orientation — horizontal, vertical, or flat. The 35 mm connection pitch matches common busbar systems.

Frequently asked questions

What is C10N3TM100C's breaking capacity at 415 V?

It has a 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2.

Where can I buy C10N3TM100C and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What standards does C10N3TM100C comply with?

It complies with EN/IEC 60947-2 and is suitable for isolation per that standard.

MPN