Skip to main content
Schneider Electric C16H32M100 — Miniature Circuit Breakers (MCB)

Schneider C16H32M100 ComPacT NSX160H, 100A, 70kA 415V

MPNC16H32M100
Obsolete

Schneider Electric ComPacT NSX NSX160H, 3P, 100 A, MicroLogic 2.2 M electronic trip unit, 70 kA Icu at 415 V AC, motor protection.

$427.21Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C16H32M100 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationMotor protection
C16H32M100 — Ratings
ParameterValue
Rated current (In)100 A at 65 °C
Poles configuration3P
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C16H32M100 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability (cycles)40000 cycles
C16H32M100 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point
C16H32M100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C16H32M100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C16H32M100 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range50...100 A
Trip unit protection functionsLSoI

Product details

Motor protection breaker with MicroLogic 2.2 M

It carries a 100 A MicroLogic 2.2 M electronic trip unit rated at 65 °C, with selectable motor tripping classes 5, 10, and 20 — so you match the thermal curve to the motor start profile (pump, fan, or high-inertia load).

Rated 100 kA Icu at 240 V AC, 70 kA at 415 V AC, and 35 kA at 525 V AC per IEC 60947-2. At 480 V AC it delivers 65 kA Icu per UL 60947-4-1. The H breaking capacity code (70 kA at 415 V) places it above the standard S rating — useful for high-fault panels where you need selectivity with upstream gear without stepping to a larger frame. The electronic trip unit provides L (long-time), So (short-time with fixed delay), and I (instantaneous) protection curves, with a 20-minute thermal memory that remembers the heat profile before and after a trip.

IP40 enclosure protection (finger-safe, not washdown). Operating altitude 0–2000 m without derating, 2000–5000 m with derating. Relative humidity 0–95 %.

Mechanical durability: 40,000 cycles. Electrical durability: 40,000 cycles at 440 V at half rated current, 20,000 cycles at full rated current, 15,000 cycles at 690 V at half current, 7,500 cycles at full 690 V. Utilisation category A (non-selectivity for short-circuit). The toggle control provides manual on/off and trip indication with a flashing green LED for ready state and red LED at 95 % Ith thermal warning.

Frequently asked questions

What is the breaking capacity of C16H32M100 at 415 V?

70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. At 480 V AC it delivers 65 kA Icu per UL 60947-4-1.

What trip unit does C16H32M100 use?

A MicroLogic 2.2 M electronic trip unit rated 100 A at 65 °C, with L (long-time), So (short-time with fixed delay), and I (instantaneous) protection, plus selectable motor tripping classes 5, 10, and 20.

Where can I buy C16H32M100?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

What compliance documentation does Schneider provide for C16H32M100?

The breaker is certified to EN/IEC 60947-2 and UL 60947-4-1. IP40 per IEC 60529, IK07 per IEC 62262. Pollution degree 3 per IEC 60664-1.

MPN