Skip to main content
Schneider Electric C60H2P50AD — 2-Pole MCB (DIN Rail)

Schneider Electric C60H2P50AD MCB, 50 A, 2P, D Curve, 10 kA

MPNC60H2P50AD
Obsolete

Schneider Electric Multi9 C60H, miniature circuit breaker, C60H2P50AD, 2P, 50 A, D curve, 10 kA Icn at 230/400 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60H2P50AD — Identification
ParameterValue
Product nameC60
Product rangeC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
C60H2P50AD — Electrical
ParameterValue
Rated current [In]50 A at 40 °C
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]12...440 V AC 50/60 Hz
Network type (AC/DC)AC DC
Network frequency50/60 Hz
C60H2P50AD — Protection
ParameterValue
Tripping curve codeD
Magnetic tripping limit10...14 x In
Breaking capacity (Icu)10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2 50 kA Icu at 250 V DC 4P conforming to IEC 60947-2
Rated service breaking capacity [Ics]7.5 kA conforming to EN 60898 - 230/400 V AC 50/60 Hz 15 kA conforming to IEC 60947-2 - 230...240 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 - 440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 400...415 V AC 50/60 Hz
Energy limitation class3 conforming to IEC 60947-2
Suitable for isolationYes conforming to IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
C60H2P50AD — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Terminal connectionsTunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid
Terminal tightening torquePower circuit: 3.5 N.m upside 3.5 N.m downside
Comb busbar / distribution block compatibilityNO
Local signalling / indicationON/OFF indication
Contact position indicatorYes
C60H2P50AD — Environmental
ParameterValue
Operating temperature range-25...60 °C
Storage temperature range-40...70 °C
Relative humidity95 % at 55 °C
C60H2P50AD — Approvals
ParameterValue
Standards / complianceEN 60898 IEC 60947-2

Product details

The C60H2P50AD is a 2-pole miniature circuit breaker from the Schneider Electric Multi9 C60H range, rated 50 A at 40 °C with a D tripping curve (magnetic trip 10–14 × In). Breaking capacity is 10 kA Icn per EN 60898 at 230/400 V AC, and under IEC 60947-2 the ultimate breaking capacity (Icu) reaches 15 kA at 400–415 V AC and 30 kA at 230–240 V AC. For a 50 A feeder in a typical commercial or light-industrial panel, 10 kA at the service entrance is adequate for most installations; the higher Icu figures confirm the breaker can clear a fault at the bus without welding contacts, even when the available fault current is higher than the Icn rating. The service breaking capacity (Ics) is 7.5 kA per EN 60898 at 230/400 V AC, meaning after clearing a fault at that level the breaker remains functional and can be reclosed — not just a one-shot device. This matters for selectivity studies: if the upstream device is a 63 A moulded-case breaker with a higher Icu, the C60H2P50AD can be coordinated to let the downstream MCB clear first.

Mounts on a 35 mm symmetrical DIN rail (EN 60715) and occupies 4 modules of 9 mm pitch — 36 mm total width. For panel builders, the 73 mm depth leaves clearance for standard 80 mm deep enclosures. The toggle handle provides local ON/OFF indication and a contact position indicator confirms the state of the moving contacts — useful for lockout/tagout verification during maintenance.

Frequently asked questions

What is the breaking capacity of C60H2P50AD?

The C60H2P50AD has a rated breaking capacity of 10 kA Icn at 230/400 V AC per EN 60898, and an ultimate breaking capacity (Icu) of 15 kA at 400–415 V AC and 30 kA at 230–240 V AC per IEC 60947-2.

What is C60H2P50AD's listed depth (73 mm) on this component line?

The C60H2P50AD has a depth of 73 mm, a width of 36 mm (4 x 9 mm pitches), and a height of 81 mm.

What compliance documentation does this brand provide for C60H2P50AD (RoHS, REACH, UL, IEC)?

The C60H2P50AD is certified to EN 60898 and IEC 60947-2. It carries tropicalisation class 2 per IEC 60068-1 and limitation class 3 per IEC 60947-2. RoHS and REACH compliance documentation is available from the manufacturer upon request.

Where can I buy C60H2P50AD?

The C60H2P50AD is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN