The Schneider Electric C60H4P6AB is a 4-pole miniature circuit breaker from the Multi9 C60H series, rated 6 A at 30 °C with a B tripping curve (3–5× In magnetic trip). It breaks 10 kA Icn at 230/400 V AC per EN 60898, and up to 15 kA Icu at 400–415 V AC per IEC 60947-2 — enough for most distribution subfeeds in commercial and light industrial panels. The B curve means the magnetic trip fires between 3 and 5 times the rated current (18–30 A for this 6 A unit), so it's a good fit for resistive or general-purpose loads where inrush stays low — lighting circuits, control transformers, small power supplies. Not the first choice for motor starting unless the motor's locked-rotor current is well under 30 A.
Depth is 73 mm, height 81 mm. Tunnel-type terminals are straightforward for a panel wireman — strip length around 12 mm, no special lug required.
Breaking capacity and service ratings
Under IEC 60947-2 the Icu reaches 15 kA at 400–415 V AC.