Schneider Electric Multi9 C60H, miniature circuit breaker, 4 poles, 6 A rated current, B curve, 10 kA breaking capacity per EN 60898, 35 mm DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60H4P6AB — Identification
ParameterValue
Product nameC60
Product rangeC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
C60H4P6AB — Electrical
ParameterValue
Rated current [In]6 A at 30 °C
Number of protected poles4
Pole configuration4P
Rated operational voltage [Ue]12...440 V AC 50/60 Hz
Network type (AC/DC)AC DC
Network frequency50/60 Hz
C60H4P6AB — Protection
ParameterValue
Tripping curve codeB
Magnetic tripping limit3...5 x In
Breaking capacity (Icu)10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2 50 kA Icu at 250 V DC 4P conforming to IEC 60947-2
Rated service breaking capacity [Ics]7.5 kA conforming to EN 60898 - 230/400 V AC 50/60 Hz 15 kA conforming to IEC 60947-2 - 230...240 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 - 440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 400...415 V AC 50/60 Hz
Energy limitation class3 conforming to IEC 60947-2
Suitable for isolationYes conforming to IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
C60H4P6AB — Mechanical
ParameterValue
9 mm pitches8
Width72 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Terminal connectionsTunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid
Terminal tightening torquePower circuit: 2 N.m upside 2 N.m downside
Comb busbar / distribution block compatibilityNO
Local signalling / indicationON/OFF indication
Contact position indicatorYes
C60H4P6AB — Environmental
ParameterValue
Operating temperature range-25...60 °C
Storage temperature range-40...70 °C
Relative humidity95 % at 55 °C
C60H4P6AB — Approvals
ParameterValue
Standards / complianceIEC 60947-2 EN 60898

Product details

The Schneider Electric C60H4P6AB is a 4-pole miniature circuit breaker from the Multi9 C60H series, rated 6 A at 30 °C with a B tripping curve (3–5× In magnetic trip). It breaks 10 kA Icn at 230/400 V AC per EN 60898, and up to 15 kA Icu at 400–415 V AC per IEC 60947-2 — enough for most distribution subfeeds in commercial and light industrial panels. The B curve means the magnetic trip fires between 3 and 5 times the rated current (18–30 A for this 6 A unit), so it's a good fit for resistive or general-purpose loads where inrush stays low — lighting circuits, control transformers, small power supplies. Not the first choice for motor starting unless the motor's locked-rotor current is well under 30 A.

Depth is 73 mm, height 81 mm. Tunnel-type terminals are straightforward for a panel wireman — strip length around 12 mm, no special lug required.

Breaking capacity and service ratings

Under IEC 60947-2 the Icu reaches 15 kA at 400–415 V AC.

Frequently asked questions

What is the breaking capacity of C60H4P6AB?

10 kA Icn at 230/400 V AC per EN 60898; under IEC 60947-2 the Icu reaches 15 kA at 400–415 V AC, 30 kA at 230–240 V AC, and 50 kA at 250 V DC (4P series).

What is the closest alternative to C60H4P6AB in the same family?

Within the Multi9 C60H series, the C60H4P6AB is the 4-pole, 6 A, B-curve variant. A direct alternative with the same pole count and rating but a different curve (C or D) would be the C60H4P6AC or C60H4P6AD — but those change the magnetic trip threshold. No pin-compatible drop-in with identical specs exists outside this order code.

MPN
C60H4P6AB