Skip to main content
Schneider Electric ENW13203 — Air Circuit Breakers

Schneider Electric ENW13203 EasyPact NW Circuit Breaker, 100

MPNENW13203
Active

Schneider Electric EasyPact NW, ENW13203, 3P drawout circuit breaker, 1000 A at 40 °C, 66 kA Icu at 440 V AC, IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ENW13203 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution
ENW13203 — Electrical ratings
ParameterValue
Rated current (In)1000 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz conforming to IEC 60947-2
Poles3P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2
ENW13203 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)55 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)75 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeC
ENW13203 — Performance
ParameterValue
Breaking time, max.35 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B
ENW13203 — Mechanical & connection
ParameterValue
Mounting modeDrawout
Mounting supportRail Base plate
Contact position indicatorYes
Width288 mm
Height322 mm
Depth277 mm
Connection pitch70 mm without spreader
Connection locationRear
ENW13203 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP30
Pollution degree3 conforming to IEC 60664-1
ENW13203 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

What this breaker delivers

The Schneider Electric ENW13203 is a 3-pole drawout circuit breaker from the EasyPact NW range, rated 1000 A at 40 °C with a breaking capacity of 66 kA Icu at 220...440 V AC 50/60 Hz per IEC 60947-2. It is a Category B breaker, meaning it is fully selective with upstream devices — the 50 kA Icw short-time withstand current (1 s) lets it ride through downstream faults without tripping, so only the faulted branch clears. For distribution duty, this selectivity is the difference between a single line down and a whole panel blackout.

Selectivity and coordination

Category B utilization (IEC 60947-2) with a 50 kA Icw for 1 s means this breaker coordinates cleanly with downstream MCCBs and fuses. Maximum breaking time is 35 ms; closing response hits 70 ms. For a panel OEM designing a selective distribution scheme, the 1000 A CT rating matches the frame size and the rear horizontal/vertical connection positions give flexibility in busbar layout.

Drawout mounting on a rail base plate — the breaker chassis stays fixed; the mechanism slides in and out for maintenance without disturbing power connections. Connection pitch is 70 mm without spreader, rear-connected. IP30 enclosure protection keeps tools and fingers out but expects panel-level sealing for washdown areas. Dimensions: 322 mm high, 288 mm wide, 277 mm deep — fits standard low-voltage switchgear compartments.

Frequently asked questions

What are the key ratings for the ENW13203?

Rated current 1000 A at 40 °C, breaking capacity 66 kA Icu at 220...440 V AC, service breaking capacity 55 kA Ics, short-time withstand 50 kA for 1 s, rated insulation voltage 1000 V AC, impulse withstand 12 kV.

Where can I buy the ENW13203?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quote.

What standards does the ENW13203 comply with?

It complies with IEC 60947-2 for circuit breakers, including Category B selectivity, pollution degree 3 per IEC 60664-1, and suitability for isolation per IEC 60947-2.

MPN