What this breaker delivers
The ENW13221 is a 4-pole drawout circuit breaker from the EasyPact NW range, rated 1600 A at 40 °C and built to IEC 60947-2. The 55 kA Ics (service breaking capacity) tells you it can reclose after that fault and keep running, not just survive once.
Drawout mounting and panel fit
Drawout mounting means the breaker chassis stays wired to the bus; the moving portion slides out for maintenance or swap without pulling cables. The footprint is 358 mm wide × 322 mm high × 277 mm deep — sit that against your existing switchgear cubicle cutout. Rear connection with a 70 mm pitch without spreader keeps phase spacing predictable for busbar drilling. IP30 is bare-enclosure; in a typical IP54 panel the door gasket handles the rest.