Skip to main content
Schneider Electric ENW24104 — Air Circuit Breakers

Schneider Electric ENW24104 EasyPact NW Circuit Breaker, 160

MPNENW24104
Active

Schneider Electric EasyPact NW, circuit breaker, ENW24104, 1600 A at 40 °C, 50 kA Icu at 440 V AC, 3P, drawout.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24104 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24104 — Electrical ratings
ParameterValue
Rated current (In)1600 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles3P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2

Breaking & withstand capacity

ENW24104 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 88 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN

Performance

ENW24104 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B

Mechanical & connection

ENW24104 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportRail
Contact position indicatorYes
Width441 mm
Height439 mm
Depth395 mm
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24104 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24104 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The Schneider Electric ENW24104 is a 3-pole EasyPact NW circuit breaker rated 1600 A at 40 °C, built for distribution duty in AC networks at 50/60 Hz. Its 50 kA Icu at 220…440 V AC (42 kA at 690 V) tells you it can safely interrupt a fault up to that level without failing — that is the short-circuit capacity that governs selectivity coordination downstream. The Ics (service breaking capacity) matches the Icu at both voltage levels, meaning after clearing a fault at rated breaking capacity the breaker remains functional, not just safe; that is a full-selectivity design, not a sacrificial one. Drawout mounting means the breaker chassis stays wired to the bus while the moving portion pulls out for inspection or swap — no need to disconnect power cables. Rear connection with a 115 mm pitch without spreader matches standard switchgear busbar spacing.

Mounts on a rail in a drawout cradle — the fixed part bolts to the enclosure frame, the moving part slides in. Dimensions: 441 mm wide, 439 mm high, 395 mm deep. That depth matters for enclosure selection — a standard 600 mm deep cabinet leaves enough room for rear cables and the arc chute clearance. Rated insulation voltage 1000 V AC and impulse withstand 12 kV give headroom for 690 V systems. The 25 ms maximum breaking time and 70 ms closing response are coordination parameters — the breaker clears fast enough to let downstream devices ride through a fault without cascading.

Frequently asked questions

What is ENW24104's breaking capacity at 440 V?

50 kA Icu (ultimate breaking capacity) and 50 kA Ics (service breaking capacity) at 220…440 V AC 50/60 Hz per IEC 60947-2. At 690 V it is 42 kA for both Icu and Ics.

What is the rated current of ENW24104?

1600 A at 40 °C ambient, with a matching 1600 A CT rating built into the breaker.

What compliance documentation does Schneider provide for ENW24104?

The breaker is certified to IEC 60947-2, with suitability for isolation per that standard. Pollution degree 4 per IEC 60664-1 is confirmed. For RoHS, REACH, and UL documentation, request the manufacturer's declaration of compliance at quote time — those are typically issued per production batch.

Where can I buy ENW24104?

The ENW24104 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

MPN