Skip to main content
Schneider Electric ENW24110 — Air Circuit Breakers

Schneider Electric ENW24110 EasyPact NW Circuit Breaker, 100

MPNENW24110
Active

Schneider Electric EasyPact NW, ENW24110, 3P circuit breaker, 1000 A at 40 °C, 50 kA Icu at 440 V AC, IEC 60947-2, fixed mount.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24110 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24110 — Electrical ratings
ParameterValue
Rated current (In)1000 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles3P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2

Breaking & withstand capacity

ENW24110 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 88 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN

Performance

ENW24110 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B

Mechanical & connection

ENW24110 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Mounting supportBase plate
Contact position indicatorYes
Width422 mm
Height352 mm
Depth297 mm
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24110 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24110 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

Its 50 kA Icu at 220…440 V AC (42 kA at 690 V) means it can safely interrupt fault currents up to that level without upstream cascading — critical for selectivity studies in low-voltage switchgear. It carries IEC 60947-2 certification, which covers the breaking capacity, utilization category B, and the 12 kV impulse withstand voltage (Uimp) that governs clearance and creepage in the panel. The IP40 enclosure keeps tools and fingers out but does not seal against water; mount it in a cabinet if washdown is nearby.

Integration — what fits and what does not

Fixed mounting on a base plate, rear connections with a 115 mm pitch without spreader. The 422 mm width, 352 mm height, and 297 mm depth mean it occupies a full compartment in a typical low-voltage switchboard — plan for a dedicated cubicle. Vertical or horizontal connection orientation is supported, but the rear-entry terminals dictate bus-bar routing behind the panel.

Key electrical ratings at a glance

Rated operational voltage (Ue) is 690 V AC; rated insulation voltage (Ui) is 1000 V AC. Short-time withstand (Icw) is 50 kA for 1 s at 440 V, 42 kA for 1 s at 690 V, and 25 kA for 3 s at 440/690 V, which supports selective coordination with downstream devices. Maximum breaking time is 25 ms; maximum closing response time is 70 ms.

Frequently asked questions

Where can I buy the ENW24110 and how is it quoted?

The ENW24110 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quote.

What is the breaking capacity of the ENW24110?

The ENW24110 has a breaking capacity (Icu) of 50 kA at 220…440 V AC and 42 kA at 690 V AC, both per IEC 60947-2.

What standards does the ENW24110 comply with?

The ENW24110 is certified to IEC 60947-2 for circuit breakers, including pollution degree 4 per IEC 60664-1.

MPN