Skip to main content
Schneider Electric ENW24131 — Air Circuit Breakers

Schneider Electric ENW24131 EasyPact NW Circuit Breaker, 320

MPNENW24131
Active

Schneider Electric EasyPact NW, ENW24131, air circuit breaker, 3200 A, 4P, 50 kA Icu at 440 V AC, IEC 60947-2.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24131 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24131 — Electrical ratings
ParameterValue
Rated current (In)3200 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2

Breaking & withstand capacity

ENW24131 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 88 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN

Performance

ENW24131 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B

Mechanical & connection

ENW24131 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Mounting supportBase plate
Contact position indicatorYes
Width537 mm
Height352 mm
Depth297 mm
Neutral pole positionLeft
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24131 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24131 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

3200 A air circuit breaker for distribution

The Schneider Electric ENW24131 is a 4-pole air circuit breaker from the EasyPact NW range, rated 3200 A at 40 °C and built for distribution duty per IEC 60947-2. The 42 kA Icu at 690 V AC covers the higher-voltage end of industrial networks. Both the ultimate (Icu) and service (Ics) breaking capacities are the same figure at each voltage — 50 kA Ics at 440 V, 42 kA Ics at 690 V — so the breaker clears its full rated fault without derating for repetitive duty.

The IP40 enclosure keeps tools and fingers out but is not washdown-rated; mount it in a cabinet if the environment is wet. Electrical durability at 440 V is 5,000 cycles without maintenance — enough for a main breaker that operates infrequently, not a switching device cycling every minute. The 25 ms maximum breaking time means the arc is quenched and the fault cleared in under three line cycles at 50 Hz.

Fixed-mount design on a base plate, rear-connected. The 537 mm width, 352 mm height, and 297 mm depth define the footprint for panel layout — account for the 115 mm connection pitch without spreader when positioning busbars. Neutral is on the left. The push-button control interface means no motor operator is built in; remote closing requires an optional add-on.

Frequently asked questions

What are the key ratings of the ENW24131?

Rated 3200 A at 40 °C, 50 kA Icu/Ics at 440 V AC, 42 kA Icu/Ics at 690 V AC, 1000 V insulation voltage, 4 poles, IP40 enclosure, and compliant with IEC 60947-2.

Where can I buy the ENW24131?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What compliance documentation does Schneider provide for the ENW24131?

The breaker is certified to IEC 60947-2 and carries a suitability-for-isolation marking per that standard. Pollution degree 4 per IEC 60664-1 is declared. Specific RoHS/REACH/UL declarations are available on request from the manufacturer.

MPN