Skip to main content
Schneider Electric ENW24152 — Air Circuit Breakers

Schneider Electric ENW24152 EasyPact NW Circuit Breaker, 160

MPNENW24152
Active

Schneider Electric EasyPact NW, circuit breaker, ENW24152, 1600 A at 40 °C, 66 kA Icu at 440 V AC, 4P, drawout, IEC 60947-2.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24152 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24152 — Electrical ratings
ParameterValue
Rated current (In)1600 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2

Breaking & withstand capacity

ENW24152 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH

Performance

ENW24152 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B

Mechanical & connection

ENW24152 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportRail
Contact position indicatorYes
Width556 mm
Height439 mm
Depth395 mm
Neutral pole positionLeft
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24152 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24152 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The Schneider Electric ENW24152 is a 4-pole EasyPact NW drawout circuit breaker rated 1600 A at 40 °C, built to IEC 60947-2 for distribution duty. The drawout cradle lets you rack the breaker out for safe maintenance or swap without disturbing the bus connections, which cuts downtime on a line-down event.

Breaking capacity and duty

The H breaking-capacity code means this unit is the high-interrupting version of the EasyPact NW frame. At 440 V the Icu is 66 kA; the Ics (service breaking capacity) is 65 kA — 98% of Icu, so it can reclose after a fault at nearly full rating without derating the next interruption. At 690 V both Icu and Ics drop to 50 kA, still adequate for most 690 V distribution. Category B utilization means the breaker is designed for selectivity with downstream devices: it withstands a let-through current without tripping, so only the faulted branch opens.

Drawout mounting on a rail support with rear connection. The 115 mm connection pitch without spreader sets the bus-bar drilling pattern. Neutral position is left.

Durability and service life

Electrical durability at 440 V is 6,000 cycles without maintenance, dropping to 4,000 at 690 V. Maximum breaking time is 25 ms; maximum closing response time is 70 ms. These numbers govern the maintenance interval: plan an inspection after 10,000 mechanical operations or 4,000 full-load breaks at 690 V, whichever comes first.

Frequently asked questions

Where can I buy ENW24152 and how do I get a price?

The ENW24152 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the key ratings of the ENW24152?

Rated 1600 A at 40 °C, 66 kA Icu at 440 V AC, 690 V operational voltage, 4 poles, drawout mounting, IEC 60947-2.

What compliance documentation does the ENW24152 meet?

The ENW24152 is certified to IEC 60947-2 and is suitable for isolation per that standard. Pollution degree 4 per IEC 60664-1 covers harsh environments.

MPN