The Schneider Electric ENW24165 is an EasyPact NW switch disconnector rated 800 A in AC-23A duty at 690 V AC, 50/60 Hz. Three-pole, drawout mounting, rear-connected. It is designed for distribution applications where you need a visible-break isolation point that can also make and break motor loads or mixed resistive-inductive circuits under load — AC-23A covers switching of motors, transformers, and capacitive loads, not just passive isolation. Rated impulse withstand voltage is 12 kV, and it carries a short-time withstand of 50 kA for 1 s (25 kA for 3 s), with a making capacity of 105 kA peak. That means it can survive a bolted fault on the load side long enough for an upstream breaker to clear — useful when coordinating with a main breaker in a switchboard. Pollution degree 4 per IEC 60664-1 means it is rated for harsh, conductive environments (dust, condensation, partial immersion) — typical in heavy industrial switchgear, not clean-room panels. IP40 enclosure protection keeps out tools and wires but not moisture ingress, so mount it inside a suitable cabinet in wet areas.
Schneider ENW24165 EasyPact NW Switch Disconnector, 800A, 3P
MPNENW24165
Active
Schneider Electric EasyPact NW switch disconnector, ENW24165, 800 A AC-23A, 3-pole, drawout, rear-connected, 395 mm depth.
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026
Specifications
| Parameter | Value |
|---|---|
| Product type | Switch disconnector |
| Range | EasyPact |
| Product range | EasyPact NW |
| Application | Distribution |
| Parameter | Value |
|---|---|
| Rated operational voltage (Ue) | 690 V AC 50/60 Hz conforming to IEC 60947-3 |
| Rated operational current (Ie) | AC-23A: 800 A AC 50/60 Hz 690 V |
| Poles | 3P |
| Rated insulation voltage (Ui) | 1000 V AC 50/60 Hz conforming to IEC 60947-3 |
| Rated impulse withstand voltage (Uimp) | 12 kV conforming to IEC 60947-3 |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Suitable for isolation | Yes conforming to IEC 60947-3 |
| Parameter | Value |
|---|---|
| Rated short-time withstand current (Icw) | 50 kA during 1 s conforming to IEC 60947-3 at -5...70 °C 25 kA during 3 s conforming to IEC 60947-3 at -5...70 °C |
| Rated short-circuit making capacity (Icm) | 105 kA AC at 50/60 Hz |
| Parameter | Value |
|---|---|
| Mechanical durability (cycles) | 20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3 |
| Electrical durability (cycles) | AC-23A: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 |
| Utilisation category | AC-23A |
| Parameter | Value |
|---|---|
| Control type | Push-button |
| Mounting mode | Drawout |
| Mounting support | Rail |
| Contact position indicator | Yes |
| Width | 441 mm |
| Height | 439 mm |
| Depth | 395 mm |
| Connection pitch | 115 mm without spreader |
| Connection location | Rear |
| Parameter | Value |
|---|---|
| Operating ambient temperature | -5...70 °C |
| Storage ambient temperature | -40...85 °C without control unit |
| IP degree of protection | IP40 |
| Pollution degree | 4 conforming to IEC 60664-1 |
| Parameter | Value |
|---|---|
| Standards | IEC 60947-3 |
Product details
Frequently asked questions
Where can I buy the ENW24165 and how do I get a price?
The ENW24165 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.
What is the ENW24165's rated operational current?
The ENW24165 is rated 800 A in AC-23A duty at 690 V AC, 50/60 Hz.
What compliance documentation does the manufacturer provide for the ENW24165?
The ENW24165 is designed to IEC 60947-3 and carries a suitability-for-isolation declaration per that standard. Pollution degree 4 per IEC 60664-1 is specified.
MPN
ENW24165