Skip to main content
Schneider Electric ENW24278 — Air Circuit Breakers

Schneider Electric ENW24278 EasyPact NW Switch Disconnector,

MPNENW24278
Active

Schneider Electric EasyPact NW, switch disconnector, ENW24278, 1000 A AC-23A, 4 poles, drawout, right neutral, IP40, IEC 60947-3.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24278 — Identification
ParameterValue
Product typeSwitch disconnector
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24278 — Electrical ratings
ParameterValue
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-3
Rated operational current (Ie)AC-23A: 1000 A AC 50/60 Hz 690 V
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-3
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-3
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-3

Breaking & withstand capacity

ENW24278 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)66 kA during 1 s conforming to IEC 60947-3 at -5...70 °C 36 kA during 3 s conforming to IEC 60947-3 at -5...70 °C
Rated short-circuit making capacity (Icm)143 kA AC at 50/60 Hz
Breaking capacity codeHA

Performance

ENW24278 — Performance
ParameterValue
Mechanical durability (cycles)20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
Electrical durability (cycles)AC-23A: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3
Utilisation categoryAC-23A

Mechanical & connection

ENW24278 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportRail
Contact position indicatorYes
Width556 mm
Height439 mm
Depth395 mm
Neutral pole positionRight
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24278 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C without control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24278 — Approvals
ParameterValue
StandardsIEC 60947-3

Product details

Switch disconnector for distribution, 1000 A continuous

The Schneider Electric ENW24278 is a 4-pole switch disconnector from the EasyPact NW range, rated 1000 A in AC-23A utilisation category at 690 V AC. Rated for continuous duty, this unit handles motor switching (AC-23A includes frequent starting and stopping of motors) and general load-break duties. The 1000 A rating at 690 V means it can switch high-power loads directly — think large pumps, compressors, or feeder circuits — without derating for the voltage step. The drawout mounting (withdrawal chassis) lets you rack the disconnector out for safe maintenance without disturbing the rear-connected power cables — a standard requirement in switchboard and MCC lineups where panel access is tight.

Fault ratings and withstand

Short-time withstand current (Icw) is 66 kA for 1 second and 36 kA for 3 seconds, both at rated operating temperature. The short-circuit making capacity (Icm) is 143 kA peak at 50/60 Hz. These numbers tell you the switch can close onto a fault and hold through a delayed upstream breaker trip — critical for selective coordination in a distribution board.

Physical integration and environment

Dimensions: 556 mm wide, 439 mm high, 395 mm deep. The rear connection pitch is 115 mm without spreader. It mounts on a rail in a drawout cradle — plan for the full depth when sizing the enclosure depth, especially with rear cable exit. Neutral is on the right side (fixed position). Connection is vertical/horizontal at the rear. The contact position indicator is visible on the front — a green/red flag that shows open/closed state without needing to open the door.

Frequently asked questions

What are the key ratings of ENW24278?

Rated operational current 1000 A in AC-23A at 690 V AC, 4 poles, drawout mounting, Icw 66 kA for 1 s, Icm 143 kA peak, Ui 1000 V, Uimp 12 kV, IP40.

What standards does ENW24278 comply with?

It complies with IEC 60947-3 for switch-disconnectors, including suitability for isolation, and IEC 60664-1 for pollution degree 4 insulation coordination.

MPN