Skip to main content
Schneider Electric EVS10H3MF60 — Air Circuit Breakers

Schneider Electric EVS10H3MF60 EasyPact EVS Circuit Breaker,

MPNEVS10H3MF60
Active

Schneider Electric EasyPact EVS, molded-case circuit breaker, EVS10H3MF60, 3-pole, 1000 A, 65 kA Icu at 440 V AC, electronic trip unit.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EVS10H3MF60 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact EVS
ApplicationDistribution
EVS10H3MF60 — Electrical ratings
ParameterValue
Rated current (In)1000 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles3P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2
EVS10H3MF60 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
EVS10H3MF60 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 5000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B
EVS10H3MF60 — Mechanical & connection
ParameterValue
Control typeManually operated
Mounting modeFixed
Mounting supportRail Base plate
Contact position indicatorYes
Width422 mm
Height352 mm
Depth297 mm
Connection pitch115 mm without spreader
Connection locationRear
EVS10H3MF60 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1
EVS10H3MF60 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

What this breaker delivers

The Schneider Electric EVS10H3MF60 is a 3-pole molded-case circuit breaker from the EasyPact EVS range, rated 1000 A at 40 °C and carrying a 65 kA Icu breaking capacity at 440 V AC (50/60 Hz) per IEC 60947-2. At 690 V the Icu drops to 50 kA — still enough for most 690 V distribution boards, but verify your fault level if you are on a high-capacity 690 V bus. The electronic trip unit — EVS Trip System6.0 — provides overload (long-time), instantaneous short-circuit, short-time short-circuit, and earth-fault protection.

Fixed-mount design with rear connection. Occupies 422 mm width × 352 mm height × 297 mm depth — factor that into your enclosure depth budget, especially if you are back-paneling with a gland plate behind it. Mounts on a rail or base plate. Connection pitch is 115 mm without a spreader; vertical or horizontal orientation is allowed. IP40 front face keeps out tools and finger probes, but the enclosure must handle the rest — this is not a washdown-rated device.

Durability and fault indication

Mechanical endurance: 20,000 cycles with maintenance, 10,000 without. Electrical endurance in Category B (distribution duty) is 5,000 cycles at 440/690 V without maintenance — this is a switchboard main or heavy feeder breaker, not a daily motor-switching device. Fault indication covers internal fault, overload, short-circuit, and earth fault — the trip unit flags the cause, so a returning technician sees what cleared the breaker without needing a separate event logger. Pollution degree 4 per IEC 60664-1 means it tolerates conductive dust and heavy condensation — suitable for industrial environments where a standard IP20 breaker might track across terminals.

Frequently asked questions

What is the breaking capacity of EVS10H3MF60 at 690 V?

50 kA Icu at 690 V AC 50/60 Hz per IEC 60947-2.

What protection functions does the EVS Trip System6.0 provide?

Overload (long-time), instantaneous short-circuit, short-time short-circuit, and earth-fault protection.

Where can I buy the EVS10H3MF60 and get current pricing?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

MPN
EVS10H3MF60