Skip to main content
Schneider Electric EZ9F34206 — 2-Pole MCB (DIN Rail)

Schneider Easy9 EZ9F34206 MCB, 6 A, 2P, C-Curve, 4.5 kA

MPNEZ9F34206
Active

Schneider Electric Easy9 series, EZ9F34206 miniature circuit breaker, 2-pole, 6 A rated current, C-curve, 4.5 kA breaking capacity, DIN-rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZ9F34206 — Identification
ParameterValue
Series / familyEasy9
Device short nameEasy9 MCB
Product / component typeMiniature circuit-breaker
Device applicationDistribution
EZ9F34206 — Electrical
ParameterValue
Rated current [In]6 A
Number of protected poles2
Rated operational voltage [Ue]400 V AC 50 Hz
Network type (AC/DC)AC
Network frequency50 Hz
EZ9F34206 — Protection
ParameterValue
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu)4500 A Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1 4500 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1
Rated service breaking capacity [Ics]4.5 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1
Suitable for isolationYes conforming to IEC 60898-1
Trip unit technologyThermal-magnetic
Operating / control typeToggle
Mechanical durability (cycles)10000 cycles
EZ9F34206 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height81 mm
Depth66.5 mm
Mounting supportDIN rail
Mounting modeClip-on
Terminal connectionsTunnel type terminal (top or bottom) 1...25 mm² rigid Tunnel type terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Local signalling / indicationWithout
Contact position indicatorYes
EZ9F34206 — Environmental
ParameterValue
Operating temperature range-25...60 °C
Storage temperature range-40...85 °C
Relative humidity95 % at -25...60 °C
EZ9F34206 — Approvals
ParameterValue
Standards / complianceIEC 60898-1

Product details

The Schneider Electric Easy9 EZ9F34206 is a 2-pole miniature circuit breaker rated 6 A with a C-curve trip characteristic (magnetic trip between 5 and 10 times In). The 4.5 kA breaking capacity at 230/400 V AC per IEC 60898-1 means it safely interrupts a fault current up to that level without welding contacts or cascading upstream — adequate for most residential and light commercial distribution boards where the prospective short-circuit current stays under that threshold. Thermal-magnetic trip technology covers both overload (thermal bimetal) and short-circuit (solenoid) protection in one unit. For motor circuits or transformers with higher inrush, a D-curve would be preferred; for purely resistive loads, a B-curve could be used. This part is sized for a 6 A final subcircuit.

The 36 mm width occupies 4 module pitches at 9 mm each — standard for a 2-pole MCB in a distribution board. Tunnel-type terminals accept 1–25 mm² rigid or 1–16 mm² flexible cable; tighten to 2 N·m. IP20 finger-safe terminals suit enclosed panel use.

Frequently asked questions

What is the breaking capacity of the EZ9F34206?

The breaking capacity is 4.5 kA Icn at both 230 V AC and 400 V AC, 50/60 Hz, conforming to IEC 60898-1. The service breaking capacity Ics is also 4.5 kA at 230 V (100% of Icn) per the same standard.

Where can I buy the EZ9F34206?

This part is available to order through independent distribution channels. Submit an RFQ for current pricing and availability — quotes are confirmed at quote time.

What standards does the EZ9F34206 comply with?

It complies with IEC 60898-1 for miniature circuit breakers, with a rated insulation voltage of 500 V AC and impulse withstand voltage of 4 kV. It is suitable for isolation per that standard.

MPN
EZ9F34206