Schneider Electric EZC100H1100 — Circuit Breaker Accessories

Schneider EasyPact EZC100H1100 1P 100A MCCB, 25kA at 240V

MPNEZC100H1100
Active

Schneider Electric EasyPact EZC100H, 1-pole 100 A thermal-magnetic MCCB, TM-D trip unit, 25 kA Icu at 240 V AC, 10 kA Icu at 125 V DC, fixed mount, toggle control.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

EZC100H1100 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution

Electrical

EZC100H1100 — Electrical
ParameterValue
Network type (AC/DC)AC DC
Rated current [In]100 A at 40 °C
Rated operational voltage [Ue]125 V DC conforming to IEC 60947-2 415 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description1P

Protection & Performance

EZC100H1100 — Protection & Performance
ParameterValue
Breaking capacity10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]5 kA at 125 V DC conforming to IEC 60947-2 12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
Trip unit technologyThermal-magnetic
Trip unit rating100 A at 50 °C
Trip unit nameTM-D
Protection typeShort-circuit protection Overload protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability13000 cycles
Local signallingPositive contact indication

Mechanical

EZC100H1100 — Mechanical
ParameterValue
Connection pitch25 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC100H
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width25 mm
Height130 mm
Depth60 mm

Environmental

EZC100H1100 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Pollution degree3 conforming to IEC 60664-1 3 conforming to IEC 947-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C

Approvals

EZC100H1100 — Approvals
ParameterValue
StandardsGB/T 14048.2 EN/IEC 60947-2 EN/IEC 60947-1 JIS C8201-2-2

Product details

It's 25 mm wide — one pole wide — so it slots into a backplate-mounted assembly without eating up rail space. The 25 kA Icu at 240 V AC means it'll clear a substantial fault on a 240 V distribution bus without upstream coordination headaches; at 415 V AC it's 5 kA Icu, so watch the system SCCR if you're using it on a 400 V line. It's a Category A breaker — no intentional short-time delay, so it's meant for instant trip on fault, not selective coordination with downstream devices.

The breaking capacity code 'H' tells you this is the high-interrupting version of the EZC100 frame. At 125 V DC it's 10 kA Icu, which covers battery-bank and UPS output breakers in telecom/DC plant applications. The IP20 finger-safe terminals and IK07 impact resistance handle the usual enclosure-installation abuse. Mechanical durability of 13,000 cycles — that's the expected life of the mechanism under no-load switching. For a distribution breaker that cycles a few times a year in normal service, that's effectively a lifetime. If you're switching it daily as a disconnect, you'll want to check the electrical endurance curve (not in this spec set) for the actual load current.

Mounting & connections

Fixed mount on a backplate — no DIN rail adapter on this one. The 25 mm pole pitch matches standard panelboard busbar spacing. Front connections both top and bottom, so busbar runs and load cables land on the same face. Connection pitch is 25 mm, which aligns with standard distribution lug kits. Toggle control with positive contact indication — you can see the contact position through the front window, not just the handle position. That matters for lockout/tagout verification.

Frequently asked questions

Where can I buy the EZC100H1100 and what is the lead time?

Sourced and quoted to order against an RFQ through our independent distribution network. Availability and current pricing confirmed at quote time.

What is the breaking capacity of the EZC100H1100 at 240 V?

25 kA Icu at 220...240 V AC 50/60 Hz per IEC 60947-2. At 415 V AC it's 5 kA Icu.

What standards does the EZC100H1100 comply with?

It complies with GB/T 14048.2, EN/IEC 60947-2, EN/IEC 60947-1, and JIS C8201-2-2. Suitable for isolation per IEC 60947-2.

What is the width of the EZC100H1100?

25 mm — single-pole width for a 1-pole MCCB.