Skip to main content
Schneider Electric EZC100H2040 — Circuit Breaker Accessories

Schneider EasyPact EZC100H2040 40A 2P MCCB, 10-100kA IC

MPNEZC100H2040
Active

Schneider Electric EasyPact EZC100H, EZC100H2040, 2-pole MCCB, 40 A rated current, TM-D thermal-magnetic trip, 10–100 kA breaking capacity, IP20.

$52.89Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

EZC100H2040 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC100H2040 — Electrical
ParameterValue
Network type (AC/DC)DC AC
Rated current [In]40 A at 40 °C
Rated operational voltage [Ue]550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description2P
EZC100H2040 — Protection & Performance
ParameterValue
Breaking capacity10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]15 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 125 V DC conforming to IEC 60947-2 5 kA at 250 V DC conforming to IEC 60947-2 50 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
Trip unit technologyThermal-magnetic
Trip unit rating40 A at 50 °C
Trip unit nameTM-D
Protection typeOverload protection Short-circuit protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability13000 cycles
Local signallingPositive contact indication
EZC100H2040 — Mechanical
ParameterValue
Connection pitch25 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC100H
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width50 mm
Height130 mm
Depth60 mm
EZC100H2040 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Pollution degree3 conforming to IEC 60664-1 3 conforming to IEC 947-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC100H2040 — Approvals
ParameterValue
StandardsGB/T 14048.2 EN/IEC 60947-1 EN/IEC 60947-2 JIS C8201-2-2

Product details

The Schneider Electric EZC100H2040 is a 2-pole EasyPact EZC100H moulded-case circuit breaker rated 40 A at 40 °C, with a TM-D thermal-magnetic trip unit. The 40 A trip rating at 50 °C means the breaker holds full load without nuisance tripping in a warm panel — the TM-D curve handles motor inrush and distribution loads. Breaking capacity varies by voltage: 100 kA Icu at 110–130 V AC, 50 kA at 220–240 V AC, 30 kA at 380–415 V AC, 20 kA at 440 V AC, and 10 kA at 550 V AC 50/60 Hz, all per IEC 60947-2. On DC, it delivers 10 kA Icu at 125 V DC (1-pole) and 250 V DC (2-pole). The H breaking-capacity code means this is the high-interrupting version of the EZC100 frame — sized for distribution panels where fault currents can hit 100 kA on low-voltage AC. IP20 finger-safe terminals and IK07 impact resistance cover handling during installation.

Deployment context

Fixed backplate mounting with front-facing connections — upside and downside both front-connect, so it panels into a distribution board or enclosure with a 25 mm connection pitch. The 2-pole format (2t protected poles, no neutral protection) suits single-phase or DC branch circuits where only the line and switched neutral need protection. Mechanical durability of 13,000 cycles fits distribution duty (not frequent switching like a contactor).

Frequently asked questions

What breaking capacity does the EZC100H2040 have at 240 V AC?

50 kA Icu at 220–240 V AC 50/60 Hz per IEC 60947-2. At 400–415 V AC it drops to 30 kA Icu, and at 440 V AC to 20 kA Icu.

What standards does the EZC100H2040 comply with?

It complies with GB/T 14048.2, EN/IEC 60947-1, EN/IEC 60947-2, and JIS C8201-2-2. It is also suitable for isolation per IEC 60947-2.

Where can I buy the EZC100H2040?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock figures or lead-time numbers are published here.

MPN
EZC100H2040