Skip to main content
Schneider Electric EZC100H4080 — Molded Case Circuit Breakers (MCCB)

Easypact EZC100H4080 MCCB, 80 A, 100 kA Icu at 240 V

MPNEZC100H4080
Active

Schneider Electric EasyPact EZC100H, EZC100H4080, 4-pole fixed MCCB, 80 A thermal-magnetic TM-D trip, 100 kA Icu at 240 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

EZC100H4080 — Identification
ParameterValue
Product / component typeCircuit breaker
Device applicationDistribution
EZC100H4080 — Mechanical
ParameterValue
Height130 mm
Width100 mm
Depth60 mm
EZC100H4080 — Electrical
ParameterValue
[In] rated current80 A at 40 °C
Breaking capacity10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity5 kA at 125 V DC conforming to IEC 60947-2 5 kA at 250 V DC conforming to IEC 60947-2 5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2
EZC100H4080 — Specifications
ParameterValue
Poles description4P
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Device short nameEasypact EZC100H
StandardsEN/IEC 60947-1 JIS C8201-2-2 GB/T 14048.2 EN/IEC 60947-2

Product details

Breaking capacity — the number that decides the fit

The EZC100H4080 carries a 100 kA Icu at 110–130 V AC and 50 kA at 220–240 V AC — meaning it can safely interrupt a fault current up to that level without welding or bursting the contacts. At 380–400 V it still holds 30 kA, and at 550 V AC it holds 10 kA. On DC sides, it is rated 10 kA at 125 V DC (1-pole) and 250 V DC (2-pole). That covers most industrial distribution panels fed by a transformer or a generator step-down.

The TM-D trip unit is thermal-magnetic — thermal for overload (inverse-time, responding to RMS heating), magnetic for short-circuit (instantaneous pick-up). The breaker is Category A (no intentional short-time delay), meaning it trips fast on a hard fault — standard for a distribution feeder or branch panel where selectivity is handled upstream with a time-delay breaker or fuse.

Fixed-mount on a backplate, front-connected both line and load. The 4-pole body is 100 mm wide, 130 mm tall, 60 mm deep — a compact footprint for a 100 kA-rated 4-pole. Connection pitch is 25 mm, which matches standard busbar spacing. IP20 finger-safe terminals are standard; the enclosure must provide the rest of the ingress protection. IK07 impact rating means it survives a 2 J hammer blow — enough for panel-door mounting if the door is not exposed to heavy tools.

The EZC100H4080 is listed as current production (active lifecycle). It is certified to EN/IEC 60947-1 and -2, JIS C8201-2-2, and GB/T 14048.2 — so it is accepted in European, Japanese, and Chinese markets.

Frequently asked questions

How do I get current pricing and availability for EZC100H4080?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the closest pin-compatible alternative to EZC100H4080 in this component family?

Within the EasyPact EZC100H series, the frame size is the same; the difference is the trip rating and breaking capacity code. The EZC100H4080 is the 80 A, H-breaking (high) variant. A lower-amp unit (e.g., 63 A) shares the same footprint and terminal layout if you need to downrate for a specific load.

What compliance documentation does this brand provide for EZC100H4080?

The breaker is certified to EN/IEC 60947-1 and -2, JIS C8201-2-2, and GB/T 14048.2. It carries an IEC 60947-2 suitability-for-isolation marking. RoHS/REACH declarations are standard for Schneider EasyPact products.

MPN
EZC100H4080