Schneider Electric EasyPact EZC100N, EZC100N1015, 1-pole thermal-magnetic circuit breaker, 15 A rated current, 25 kA breaking capacity at 110-130 V AC, IP20, backplate mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

EZC100N1015 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC100N1015 — Electrical
ParameterValue
Network type (AC/DC)DC AC
Rated current [In]15 A at 40 °C
Rated operational voltage [Ue]125 V DC conforming to IEC 60947-2 415 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description1P
EZC100N1015 — Protection & Performance
ParameterValue
Breaking capacity25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 18 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 9 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 1.25 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 1.25 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN
Trip unit technologyThermal-magnetic
Trip unit rating15 A at 50 °C
Trip unit nameTM-D
Protection typeShort-circuit protection Overload protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability13000 cycles
Local signallingPositive contact indication
EZC100N1015 — Mechanical
ParameterValue
Connection pitch25 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC100N
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width25 mm
Height130 mm
Depth60 mm
EZC100N1015 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Pollution degree3 conforming to IEC 60664-1 3 conforming to IEC 947-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC100N1015 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 JIS C8201-2-2 GB/T 14048.2 EN/IEC 60947-1

Product details

The Schneider Electric EZC100N1015 is a 1-pole thermal-magnetic circuit breaker from the EasyPact EZC100N series, rated 15 A at 40 °C (15 A at 50 °C with the TM-D trip unit). It's built for distribution duty in fixed-mount panels — backplate mounted, front-connected, and toggled manually. The 25 mm width per pole keeps the rail density tight; a 13000-cycle mechanical durability means it'll outlast most panel refreshes.

The EZC100N1015 carries a 25 kA Icu at 110-130 V AC and 18 kA at 220-240 V AC per IEC 60947-2. That's the N breaking capacity code — enough for most secondary distribution panels behind a larger main breaker. At 400-415 V AC it drops to 2.5 kA, so if your line side is 400 V with high fault current, this needs upstream coordination. The 5 kA at 125 V DC (1-pole) covers DC bus or battery circuits.

Fixed backplate mount, 25 mm pitch per pole, front connections top and bottom. IP20 finger-safe terminals, pollution degree 3 rated — fine for a clean panel environment. The toggle actuator gives positive contact indication; the thermal-magnetic trip handles both overload and short-circuit without an external relay.

Frequently asked questions

Where can I buy EZC100N1015 and how do I get a price?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is EZC100N1015's breaking capacity at 240 V?

18 kA Icu at 220-240 V AC per IEC 60947-2.

What compliance documentation does this brand provide for EZC100N1015?

The breaker is certified to EN/IEC 60947-2, JIS C8201-2-2, and GB/T 14048.2. It carries IP20 and IK07 protection ratings and is suitable for isolation per IEC 60947-2.

MPN