Skip to main content
Schneider Electric EZC100N1100 — Circuit Breaker Accessories

Schneider Electric EZC100N1100 EasyPact EZC100N, 100 A, 1-Po

MPNEZC100N1100
Obsolete

Schneider Electric EasyPact EZC100N, MCCB, 1 pole, 100 A, thermal-magnetic TM-D trip unit, breaking capacity 25 kA at 110-130 V AC, front connections, IP20, backplate mount.

$39.96Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZC100N1100 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC100N1100 — Electrical
ParameterValue
Network type (AC/DC)AC DC
Rated current [In]100 A at 40 °C
Rated operational voltage [Ue]125 V DC conforming to IEC 60947-2 415 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description1P
EZC100N1100 — Protection & Performance
ParameterValue
Breaking capacity25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 18 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 9 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 1.25 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 1.25 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN
Trip unit technologyThermal-magnetic
Trip unit rating100 A at 50 °C
Trip unit nameTM-D
Protection typeShort-circuit protection Overload protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability13000 cycles
Local signallingPositive contact indication
EZC100N1100 — Mechanical
ParameterValue
Connection pitch25 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC100N
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width25 mm
Height130 mm
Depth60 mm
EZC100N1100 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Pollution degree3 conforming to IEC 60664-1 3 conforming to IEC 947-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC100N1100 — Approvals
ParameterValue
StandardsJIS C8201-2-2 GB/T 14048.2 EN/IEC 60947-1 EN/IEC 60947-2

Product details

The EZC100N1100 is a 1-pole EasyPact EZC100N moulded-case circuit breaker rated 100 A at 40 °C (trip unit rating 100 A at 50 °C) with a thermal-magnetic TM-D trip unit. It provides short-circuit and overload protection in distribution panels. The breaking capacity varies by voltage: 25 kA Icu at 110–130 V AC, 18 kA at 220–240 V AC, and 2.5 kA at 400–415 V AC — so at 400 V line-to-line the fault-interrupt rating drops sharply; selectivity studies need the 2.5 kA figure, not the 25 kA headline. Rated operational voltage covers 125 V DC (1-pole) and 415 V AC 50/60 Hz; insulation voltage is 690 V AC.

IP20 finger protection on the front face; IK07 impact resistance means it withstands a 2 J hammer blow — adequate for panel-door mounting where accidental tool strikes occur.

Frequently asked questions

How do I get current pricing and availability for EZC100N1100?

Submit an RFQ through this listing. The part is sourced to order through independent distribution; pricing and lead time are confirmed at quote time.

What compliance documentation does this brand provide for EZC100N1100?

The breaker is designed to JIS C8201-2-2, GB/T 14048.2, EN/IEC 60947-1, and EN/IEC 60947-2. The manufacturer typically provides IEC declaration of conformity; request material certs at RFQ time.

What is EZC100N1100's listed depth (60 mm) on this component line?

The depth is 60 mm, width 25 mm, height 130 mm — fits standard distribution board cutouts with front-connection clearance.

MPN