EZC250H3175 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC250H3175 — Electrical
ParameterValue
Network type (AC/DC)DC AC
Rated current [In]175 A at 40 °C
Rated operational voltage [Ue]550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description3P
EZC250H3175 — Protection & Performance
ParameterValue
Breaking capacity10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 125 V DC 1P conforming to IEC 60947-2 30 kA Icu at 250 V DC 2P conforming to IEC 60947-2 36 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 125 V DC conforming to IEC 60947-2 15 kA at 250 V DC conforming to IEC 60947-2 18 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 42.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 42.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
Trip unit technologyThermal-magnetic
Trip unit rating175 A at 50 °C
Trip unit nameTM-D
Protection typeShort-circuit protection Overload protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability10000 cycles
Local signallingPositive contact indication
EZC250H3175 — Mechanical
ParameterValue
Connection pitch35 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC250H
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width105 mm
Height165 mm
Depth60 mm
EZC250H3175 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Pollution degree3 conforming to IEC 60664-1 3 conforming to IEC 947-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC250H3175 — Approvals
ParameterValue
StandardsGB/T 14048.2 EN/IEC 60947-1 EN/IEC 60947-2

Product details

The Schneider Electric EZC250H3175 is an EasyPact EZC250H circuit breaker — a 3-pole, 175 A thermal-magnetic unit with a TM-D trip block, built for distribution duty in fixed-mount backplate panels. It carries a 36 kA Icu at 400 V AC (IEC 60947-2) and a 25 kA Icu at 440 V AC, so it clears faults up to that level without cascading upstream. IP20 finger-safe terminals and IK07 impact resistance suit it for enclosed switchboards where incidental contact is the only exposure.

The H breaking-capacity code means this breaker handles 36 kA Icu at 380–415 V AC (the common 400 V class) and 85 kA Icu at 220–240 V AC. On DC circuits it manages 30 kA Icu at 125 V DC (1P) or 250 V DC (2P). These numbers govern coordination with downstream devices — the high Icu at 240 V AC lets it serve as a main breaker in a split-bus panel where the utility fault current is high, while the 10 kA Icu at 550 V AC covers 480 V delta feeds.

Integration notes

Fixed-mount backplate installation — no DIN-rail adapter. Dimensions: 165 mm height, 105 mm width, 60 mm depth. The toggle handle provides positive contact indication, so at a glance you see whether the contacts are open or closed.

Frequently asked questions

What is the breaking capacity of EZC250H3175 at 400 V AC?

At 400–415 V AC 50/60 Hz the Icu is 36 kA per IEC 60947-2. At 440 V AC it is 25 kA; at 550 V AC it is 10 kA.

What is the closest alternative to EZC250H3175 in the EasyPact family?

The EZC250H3175 is the current catalog number for a 175 A, 3-pole, H-breaking-capacity EasyPact EZC250H. No pin-compatible alternative exists within the same series — the trip unit rating and frame size are specific to this variant.

Where can I buy EZC250H3175?

The EZC250H3175 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What compliance documentation does EZC250H3175 carry?

The breaker is certified to GB/T 14048.2, EN/IEC 60947-1, and EN/IEC 60947-2. RoHS and REACH declarations are available from the manufacturer on request.

MPN
EZC250H3175